| Plan Review Notes For Permit 00110302 |
| Permit Number |
00110302 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE RISER DIGRAM. AIC | | | RATING IS GIVEN FOR BREAKERS BUT NOT | | | FOR MAIN DISCONNECT. PLEASE SHOW AIC | | | RATING FOR MAIN. PER 110-9 | | | | | | 2)NOTE: PLEASE SEE NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSIDE AND OUT | | | -SIDE ALL SLEEPING ROOMS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|