| Plan Review Notes For Permit 00110282 |
| Permit Number |
00110282 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE PROVIDE AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | PER 110-9. | | | | | | 2)NOTE: PLEASE PROVIDE CALCULATION TO | | | INCLUDE LARGEST MOTOR AT 125%. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION | | | OF EQUIPMENT GROUNDING CONDUCTORS OR | | | CONDUIT TYPE AFTER FIRST MEANS OF DISC- | | | -ONNECT. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|