| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2002-08-23 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | AND MAKE ANY NECESSARY CHANGES IN THE | | | PLANS FOR THE NEXT REVISIONS. | | | | | | 1} THE LOAD CALCULATIONS DID NOT CHANGE | | | ON THESE REVISIONS,PLEASE MAKE CHANGES | | | IN NEXT REVISION. | | | | | | 2} WATER HEATER ON E-2 IS NOT SHOWN IN | | | THE CALC'S ON THE SCHEDULE. | | | | | | 3} WHERE IS CIRCUIT K-39 FOR THE FIRE | | | SUPPRESSION? | | | | | | 4} THE TYPE "J" FIXTURES DESIGNATIONS | | | CHANGED,AND ARE NOT LISTED ON THE | | | REVISIONS AS SHEET E-8 WAS | | | MISSING.PLEASE SUPPLY INFORMATION FOR | | | THESE FIXTURES. | | | | | | 5} CIRCUIT K-62 IS LISTED TWICE ON E-1. | | | THE CONTRACTOR INDICATED THE ONE IN THE | | | DISHWASHER AREA WAS ON CIRCUIT K-42 BUT | | | THAT CIRCUIT FEEDS THE BATH AREAS,AND | | | THE CALC FOR THAT CIRCUIT DIDN'T CHANGE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|