2002-08-23 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND MAKE ANY NECESSARY CHANGES IN THE
 PLANS FOR THE NEXT REVISIONS.
  
 1} THE LOAD CALCULATIONS DID NOT CHANGE
 ON THESE REVISIONS,PLEASE MAKE CHANGES
 IN NEXT REVISION.
  
 2} WATER HEATER ON E-2 IS NOT SHOWN IN
 THE CALC'S ON THE SCHEDULE.
  
 3} WHERE IS CIRCUIT K-39 FOR THE FIRE
 SUPPRESSION?
  
 4} THE TYPE "J" FIXTURES DESIGNATIONS
 CHANGED,AND ARE NOT LISTED ON THE
 REVISIONS AS SHEET E-8 WAS
 MISSING.PLEASE SUPPLY INFORMATION FOR
 THESE FIXTURES.
  
 5} CIRCUIT K-62 IS LISTED TWICE ON E-1.
 THE CONTRACTOR INDICATED THE ONE IN THE
 DISHWASHER AREA WAS ON CIRCUIT K-42 BUT
 THAT CIRCUIT FEEDS THE BATH AREAS,AND
 THE CALC FOR THAT CIRCUIT DIDN'T CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392