| 2001-11-28 00:00:00 | DENIED (SEVENTH TIME) |
| | REFERENCE: SPC-94 - SGC-97 - FACBC-97 |
| | |
| | 1) DEPT OF HOTEL BUSINESS REGULATION |
| | PLAN REVIEW W/COMMENTS REQUIRED BEFORE |
| | PLUMBING PLAN REVIEW. CONTACT FOR |
| | APPOINTMENT. (954) 958-5520 |
| | 2) SHT A1.3 (CHANGED FROM A2.1) MEN & |
| | WOMEN RESTROOMS PREVIOUS COMMENT RE: |
| | DCA-FLBC RULE 9B-7.0042 FL ADM. CODE, |
| | SEC 4.17.3 FIG 30(E). CLEAR FLOOR SPACE |
| | FOR W/C AND LAV. |
| | 3) SHT A10.1, EMPLOYEE REST RM, SHOWER |
| | STALL, COMPLY W/SEC 4.21 ADA SHOWER |
| | STALL. SHOW DETAILS (FM PREVIOUS P-REV.) |
| | 4) FM PREVIOUS REVIEW, SHT A2.1, A2.M1, |
| | COMPLY WITH SEC 4.1.3(19)(A). ADA FIXED |
| | SEATING IN A RESTURANT. NO DETAILS SHOWN |
| | 5) FM PREVIOUS REVIEW,SHT M2.1.2.3, CON- |
| | DENSATE FROM 7-AHU, PROVIDE AN ISOMETRIC |
| | DRAWING OF A COMMON COLLECTION SYSTEM TO |
| | A DRY WELL OR STORM DRAIN WITH A RELIEF |
| | VINT. SEC 804.3, 104. |
| | 6) FM PREVIOUS REVIEW. SEE ATTACHED GAS |
| | PERMIT APPLICATION REQUIREMENTS. ADDRESS |
| | #'S 1-3-7 & 9 FOR PLAN REVIEW. (ELECT. |
| | W/HEATER) |
| | 7) FM PREVIOUS REVIEW. SHT P1.7 DETAIL |
| | #10 FUNNEL DRAIN, FLOOR SINKS REQUIRED |
| | FOR ALL INDIRECT WASTE. S-802. FD STILL |
| | SHOWN FOR WALK IN COOLERS SHT'S P1, P4, |
| | & P6. |
| | 8) FM PREVIOUS REVIEW. DETAIL FOR ICE |
| | MACHINE NOT SHOWN. CONDENSER UNIT AND |
| | ICE BIN DRAINS TO BE SEPARATED. CROSS |
| | CONNECTION OF CONTAMINATED WASTE. SEC |
| | 804 FOOD HANDLING. |
| | 9) SHT P.1 ITEM #14 SMOKE HOG. INDIRECT |
| | WASTE TO COMPLY WITH SPC SEC 805.1.1 & |
| | 805.1.2 |
| | 10) SHT P.1 ITEMS # 6 AND 22 NOT FOUND. |
| | 11) SHT P.3 #'S 6 & 7, WATER HAMMERAR- |
| | RESTORS TO BE LOCATED NEAR FIXTURES NOT |
| | AT TOP OF DROPS AS SHOWN. "IN AN EFFECT- |
| | IVE RANGE OF FIXTURE." |
| | 12) SHT P.4 BACK TO BACK LAVS NOT VENTED |
| | (LAV-2) |
| | 13) SHT P.4 GAS ISOMETRIC DIAGRAM. UNION |
| | REQUIRED BETWEEN MANUAL VALVE AND SOLIN- |
| | OID VALVE.(#'S 7 AND 8). ALSO RE: FS-1 |
| | ITEM #7 NOT SHOWN ON ISOMETRIC. |
| | 14) SHT P.8 #58 HUB DRAIN NOT APPROVED. |
| | 15) SHT P.8 #53 NO POLYETHYLENE JACKET |
| | FOR UNDERGROUND PIPING. REF STD GAS CODE |
| | 1997 ONLY FOR GAS INSTALLATION. |
| | 16) SHT P.8 #14 BACKFLOW REQUIRED FOR |
| | TEMP CONSTRUCTION WATER. |
| | 17) SHT FS-1 ITEM #2, DEEP FAT FRYER |
| | SHALL NOT DRAIN INTO GREASE LINE. |
| | 18) SHT FS-1 ITME #4, CHINESE RANGE. |
| | WASTE WATER WHEN DISCHARGED INTO THE |
| | BUILDING DRAINAGE SYSTEM SHALL BE AT A |
| | TEMPERATURE NOT HIGHER THAN 140 DEGREES |
| | F. SPC SEC 717.8 |
| | 19) SHT FS-1 ITEM #20.1 NSF APPROVAL RE- |
| | QUIRED FOR FILTER. PROVIDE DETAILS. |
| | 20) SHT FS-1 ITEM #41.2, 43.1 & 43.2 NOT |
| | SHOWN. |
| | 21) SHEETS REFERED TO IN PREVIOUS REVIEW |
| | (6TH) DO NOT APPEAR ON PLANS SUBMITTED |
| | FOR THIS REVIEW. PLEASE KEEP PAGES UNI- |
| | FORM FROM REVIEW TO REVIEW TO EXPIDITE |
| | THE REVIEW PROCESS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561)- 659-8096 EXT 8377 |