Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop P
Sequence Number 7
Notes
Date Text
2001-11-28 00:00:00DENIED (SEVENTH TIME)
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW W/COMMENTS REQUIRED BEFORE
 PLUMBING PLAN REVIEW. CONTACT FOR
 APPOINTMENT. (954) 958-5520
 2) SHT A1.3 (CHANGED FROM A2.1) MEN &
 WOMEN RESTROOMS PREVIOUS COMMENT RE:
 DCA-FLBC RULE 9B-7.0042 FL ADM. CODE,
 SEC 4.17.3 FIG 30(E). CLEAR FLOOR SPACE
 FOR W/C AND LAV.
 3) SHT A10.1, EMPLOYEE REST RM, SHOWER
 STALL, COMPLY W/SEC 4.21 ADA SHOWER
 STALL. SHOW DETAILS (FM PREVIOUS P-REV.)
 4) FM PREVIOUS REVIEW, SHT A2.1, A2.M1,
 COMPLY WITH SEC 4.1.3(19)(A). ADA FIXED
 SEATING IN A RESTURANT. NO DETAILS SHOWN
 5) FM PREVIOUS REVIEW,SHT M2.1.2.3, CON-
 DENSATE FROM 7-AHU, PROVIDE AN ISOMETRIC
 DRAWING OF A COMMON COLLECTION SYSTEM TO
 A DRY WELL OR STORM DRAIN WITH A RELIEF
 VINT. SEC 804.3, 104.
 6) FM PREVIOUS REVIEW. SEE ATTACHED GAS
 PERMIT APPLICATION REQUIREMENTS. ADDRESS
 #'S 1-3-7 & 9 FOR PLAN REVIEW. (ELECT.
 W/HEATER)
 7) FM PREVIOUS REVIEW. SHT P1.7 DETAIL
 #10 FUNNEL DRAIN, FLOOR SINKS REQUIRED
 FOR ALL INDIRECT WASTE. S-802. FD STILL
 SHOWN FOR WALK IN COOLERS SHT'S P1, P4,
 & P6.
 8) FM PREVIOUS REVIEW. DETAIL FOR ICE
 MACHINE NOT SHOWN. CONDENSER UNIT AND
 ICE BIN DRAINS TO BE SEPARATED. CROSS
 CONNECTION OF CONTAMINATED WASTE. SEC
 804 FOOD HANDLING.
 9) SHT P.1 ITEM #14 SMOKE HOG. INDIRECT
 WASTE TO COMPLY WITH SPC SEC 805.1.1 &
 805.1.2
 10) SHT P.1 ITEMS # 6 AND 22 NOT FOUND.
 11) SHT P.3 #'S 6 & 7, WATER HAMMERAR-
 RESTORS TO BE LOCATED NEAR FIXTURES NOT
 AT TOP OF DROPS AS SHOWN. "IN AN EFFECT-
 IVE RANGE OF FIXTURE."
 12) SHT P.4 BACK TO BACK LAVS NOT VENTED
 (LAV-2)
 13) SHT P.4 GAS ISOMETRIC DIAGRAM. UNION
 REQUIRED BETWEEN MANUAL VALVE AND SOLIN-
 OID VALVE.(#'S 7 AND 8). ALSO RE: FS-1
 ITEM #7 NOT SHOWN ON ISOMETRIC.
 14) SHT P.8 #58 HUB DRAIN NOT APPROVED.
 15) SHT P.8 #53 NO POLYETHYLENE JACKET
 FOR UNDERGROUND PIPING. REF STD GAS CODE
 1997 ONLY FOR GAS INSTALLATION.
 16) SHT P.8 #14 BACKFLOW REQUIRED FOR
 TEMP CONSTRUCTION WATER.
 17) SHT FS-1 ITEM #2, DEEP FAT FRYER
 SHALL NOT DRAIN INTO GREASE LINE.
 18) SHT FS-1 ITME #4, CHINESE RANGE.
 WASTE WATER WHEN DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A
 TEMPERATURE NOT HIGHER THAN 140 DEGREES
 F. SPC SEC 717.8
 19) SHT FS-1 ITEM #20.1 NSF APPROVAL RE-
 QUIRED FOR FILTER. PROVIDE DETAILS.
 20) SHT FS-1 ITEM #41.2, 43.1 & 43.2 NOT
 SHOWN.
 21) SHEETS REFERED TO IN PREVIOUS REVIEW
 (6TH) DO NOT APPEAR ON PLANS SUBMITTED
 FOR THIS REVIEW. PLEASE KEEP PAGES UNI-
 FORM FROM REVIEW TO REVIEW TO EXPIDITE
 THE REVIEW PROCESS.
  
 REVIEW BY KEN STEVENS
 (561)- 659-8096 EXT 8377