| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2001-12-21 00:00:00 | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLERS. | | | PROVIDE PLANS AND ALL MANUFACURER | | | SUBMITTAL DATA AND PRODUCT APPROVALS | | | WITH PERMIT APPLICATION. | | | | | | PLEASE NOTE, THE GREASE DUCT SHALL BE | | | DESIGNED AND INSTALLED IN A MANNER TO | | | PROVIDE AN AIR VELOCITY WITHIN THE DUCT | | | SUSTEM OF NOT LESS THAN 1,500 FT PER | | | MINUTE. 1997 SMC 505.7 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|