| 2001-07-22 00:00:00 | PLUMBING PLAN REVIEW DENIED (SIXTH TIME) |
| | NOTE ON PLANS,NEW PLANS SUBMITTED. |
| | (1) DEPT. OF HOTEL BUSINESS REGULATION |
| | PLAN REVIEW W/COMMENTS REQUIRED, BEFORE |
| | PLUMBING PLAN REVIEW.CONTACT FOR APPOINT |
| | MENT 954-958-5520. |
| | (2) SHT A2.1,A2.M1 MEN & WOMEN REST RM'S |
| | PREVIOUS COMMENT RE: HANDICAP STALLS |
| | SEE REVISION: DCA-FLBC,RULE 9B-7.0042, |
| | FL ADM.CODE, SEC 4.17.3.FIG 30(E). |
| | CLEAR FLOOR SPACE FOR W/C AND LAVATORY. |
| | (3) SHT A2.1 EMPLOYEE REST RM, SHOWER |
| | STALL, COMPLY W/SEC 4.21, ADA SHO.STALL. |
| | (3)SHT A2.1,A2.M1, COMPLY WITH SEC 4.1.3 |
| | (19)(A).ADA FIXED SEATING IN A RESTURANT |
| | (4) SHT A1.2 DETAIL ADA (A)(A1).NOT CUR- |
| | RENT.SEE NOTE 2 ABOVE. |
| | (5) SHT A10.2 HANDICAP URINAL SEC 4.18.3 |
| | CLEAR FLR SPACE 30"X 48". |
| | (6) SHT E3.3 LOCATION OF WTR/HTR, TYPE |
| | IS NOT CLEAR IF THIS IS ELECTRIC OR GAS |
| | W/H, SHT A2.0 SHOWS ELECTRIC, SHT P1.6 |
| | SHOWS GWH ON A ELECTRIC W/H SCHEDULE? |
| | (7) SHT M2.1.2.3, CONDENSATE FROM 7-AHU. |
| | PROVIDE A ISOMETRIC DRAWING OF A COMMON |
| | COLLECTION SYSTEM TO A DRY WELL OR STORM |
| | DRAIN, WITH A RELIEF VENT,SEC,804.3,104. |
| | (8A) SHT P1.5 SEC 104.3 PLANS REQUIRED. |
| | PROVIDE ISOMETRIC DRAWINGS FOR THE GAS |
| | PIPING AND SANITARY DWV. |
| | (8B) SEE ATTACHED GAS PERMIT APPLICATIO |
| | REQUIRMENTS, ADDRESS EA OF (10) ITEMS, |
| | FOR PLAN REVIEW. |
| | (9) SEC 104.3 PROVIDE KITCHEN EQUIPMENT |
| | PLANS , WITH EQUIPMENT SCHEDULE,LAY OUT. |
| | (10A)SHT P1.3,SEC 802 ALL INDIRECT WASTE |
| | TO FLR SINKS,SAFE WASTE NOT ALLOWED. |
| | (10B) SUSHI BAR, STILL NO VENT SHOWN. |
| | (11A) SHT P1,4 WATER PIPING ISOMETRIC. |
| | (MCWC94) SHOW PIPE SIZES, NO MORE THAN 2 |
| | FIXTURES ON 1/2" C/W, NO MORE THAN 4 |
| | FIXTURES ON 1/2" H/W. |
| | (11B) SHT-P1.4 SHOWS AIR CHAMBERS, |
| | SHT P1.6 REFERENCES WATER HAMMER ARREST- |
| | ORS, REMOVE AIR CHAMBERS AND REFERENCE |
| | THE WATER HAMMER ARRESTORS, AS LISTED. |
| | (12) SHT P1.5 ISOMETRIC INCORRECTLY |
| | LABLED,SHOULD BE GREASE WASTE. |
| | (13A)SHT P1.6 PLBG NOTES #14, DIELECTRIC |
| | UNIONS, NOT ALLOWED, SEC 608,MATERIALS. |
| | (13B) FOOD SERVICE NOTE #2-7"TO 11" W/C, |
| | FL PUBLIC UTILITIES SUPPLIES 12"-14"W/C. |
| | (14A) SHT P1.7 DETAIL #10 FUNNEL DRAIN, |
| | FLOOR SINKS FOR ALL INDIRECT WASTE.S-802 |
| | (14B) DETAIL #18 UNIONS IN CEILING, NOT |
| | PERMITED. NFPA-54 SEC 3.4.2 |
| | (14C) DETAIL #21 ICE MACHINE, CONDENSER |
| | UNIT & ICE BIN DRAINS,TO BE SEPERATED, |
| | CROSS CONNECTION OF CONTAMINATED WASTE. |
| | SEC 804 FOOD HANDLING. |
| | (14D) DETAIL #22, NO VENT ON WATER HTR. |
| | (15)SHT P1.3 DISHWASHER DRAIN CONNECT |
| | I/D TO SANI.SEWER, LOCAL ORD.#2938-96. |
| | END OF COMMENTSPAUL SCHMITZ |