| 2001-11-29 00:00:00 | *******************DENIED*************** |
| | |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.PLAN SHEET AC.8, OUTSIDE AIR |
| | RECAPULATION REFLECTS RTU'S.NO |
| | RTU'S OR OUTSIDE AIR REFLECTED ON |
| | PLANS. |
| | |
| | 2.PLAN SHEET AC.2, PROVIDE DETAIL OF |
| | ITEM 4 SOUND LINED PLENUM. |
| | |
| | 3.INDICATE ACCESSIBLITY FOR SERVICE |
| | FOR AHU'S 1,2, & 3. |
| | |
| | 4.PLEASE CLARIFY "PH-1,2,3,& 4", |
| | PROVIDE DETAIL OF RISER TO PENTHOUSE |
| | |
| | 5.IDENTIFY KITCHEN EXHAUST TERMINATION |
| | PLEASE NOTE AS PER 1997 SMC 506.1, |
| | DUCTS SERVING COMMERCIAL FOOD |
| | COOKING AND PROCESSING, SHALL |
| | TERMINATE OUTSIDE OF THE BUILDING |
| | AND BE LOCATED 10' FROM ANY ADJACENT |
| | PROPERTY LINE, PARKING AREA, A |
| | ADJACENT BUILDING, WINDOW, DOOR, OR |
| | AIR INTAKE OPENING AND SHALL BE A |
| | MIN. OF 40" ABOVE THE ROOF SURFACE. |
| | |
| | 5.PROVIDE MANUFACTURER SUBMITTAL DATA |
| | FOR THE SMOG HOG. |
| | |
| | 6.FIRE DAMPER DETAIL-PLAN SHEET AC.5, |
| | INDICATES VERTICLE PENERATION.FIRE |
| | DAMPERS DEPICTED ON PLAN SHEET AC.3 |
| | ARE FLOOR/CEILING PENETRATIONS. ALL |
| | FIRE DAMPERS SHALL COMPLY WITH UL |
| | 555. |
| | |
| | ADDITIONAL PLANS AND PERMITS REQUIRED |
| | FOR HOOD, FIRE SUPRESSION AND WALK-IN |
| | COOLERS.PLEASE SUBMIT MANUFACTURER |
| | SUBMITTAL DATA AND PLANS WITH PERMIT |
| | APPLICATION. |
| | |
| | PLEASE NOTE, A LETTER FROM THE ENGINEER |
| | AND OR ARCHITECT ADDRESSING COMMENTS AND |
| | INDICATING CHANGES AND RESPONSES TO |
| | COMMENTS WOULD GREATLY HELP EXPEDITE |
| | PLANS IN THE FUTURE. |
| | |