Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop FIRE
Sequence Number 6
Notes
Date Text
2001-11-26 00:00:001) IT WOULD APPEAR THAT ADDITIONAL
 EXIT SIGN(S) ARE NEEDED FOR THE
 MEZZANINE.
 2) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 3) TABLES AND CHAIRS IN MAIN DINING
 AREA ARE TOO CLOSE TOGETHER.
 4) SOME SOFFITS ARE SHOWN AT 6 FEET 8
 INCHES FROM THE FLOOR WHICH CONFLICTS
 WITH THE STANDARD BUILDING CODE,
 MINIMUM HEADROOM REQUIREMENTS. PLEASE
 DETERMINE PROBLEM AREAS.
 4) MAXIMUM TRAVEL DISTANCE IN
 SPRINKLER PROTECTED ASSEMBLY OCCUPANCIES
 IS 200 FEET.
 5) A SEPARATE FIRE ALARM PANEL IS
 NOT NECESSARY FOR TSUNAMI. THE FIRE
 ALARM EQUIPMENT SHOULD BE CONNECTED
 TO THE TOWER'S FIRE ALARM CONTROL
 PANEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910