| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
FIRE |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-11-26 00:00:00 | 1) IT WOULD APPEAR THAT ADDITIONAL | | | EXIT SIGN(S) ARE NEEDED FOR THE | | | MEZZANINE. | | | 2) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. | | | 3) TABLES AND CHAIRS IN MAIN DINING | | | AREA ARE TOO CLOSE TOGETHER. | | | 4) SOME SOFFITS ARE SHOWN AT 6 FEET 8 | | | INCHES FROM THE FLOOR WHICH CONFLICTS | | | WITH THE STANDARD BUILDING CODE, | | | MINIMUM HEADROOM REQUIREMENTS. PLEASE | | | DETERMINE PROBLEM AREAS. | | | 4) MAXIMUM TRAVEL DISTANCE IN | | | SPRINKLER PROTECTED ASSEMBLY OCCUPANCIES | | | IS 200 FEET. | | | 5) A SEPARATE FIRE ALARM PANEL IS | | | NOT NECESSARY FOR TSUNAMI. THE FIRE | | | ALARM EQUIPMENT SHOULD BE CONNECTED | | | TO THE TOWER'S FIRE ALARM CONTROL | | | PANEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|