| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-11-21 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE 700-12E CIRCUITS | | | FOR EM LTS, EXIT LTS SHALL BE FROM SAME | | | PANEL. | | | | | | | | | | | | | | | | | | | | | | | | 3)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS ARE TO BE SHOWN AT 125%. | | | 215-2/230-42 ETC. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PER 220-11/220-3/220-10/220-13 ETC. | | | | | | 5)NOTE: PLEASE CLARIFY ATTACHMENT FOR | | | TRANSFORMER. PER 250-24 | | | | | | 6)NOTE: PLEASE NOTE OUTLET SPACING TO | | | MEET LOCAL CODE ON ALL LEVELS. | | | 210-50 PBCAC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR] | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIEW | | | 561-659-8096 EXT 8372 |
|