| 2001-11-16 00:00:00 | BUILDING PLAN EVIEW |
| | PERMIT# 00110258 |
| | 651 OKEECHOBEE BLVD. # 100 |
| | ARCH: HARTER-ADAMS P.A. |
| | TEL: (407) 647-5767 |
| | FAX: (407) 647-2062 |
| | "TSUNAMI" |
| | 1)- ADDITIONAL INFORMATION REQUIRED |
| | SBC 104.2.2: STRUCTURAL SHEETS INDICATE |
| | VARIOUS FOOTINGS THAT WILL SIT UPON THE |
| | FOUNDATION FOR THE SHELL OF THE WHOLE |
| | BUILDING. WE WILL REQUIRE A LETTER FROM |
| | THE ENGINEER OF RECORD (FOR THE SHELL OF |
| | THE BUILDING) APPROVING THE ADDITIONAL |
| | LOADS BEING TRANSFERRED ONTO THE EXIST- |
| | ING FOUNDATION. |
| | THIS WAS A REQUEST FROM PLAN REVIEW COM- |
| | PLETED 01/16/2001. A LETTER WAS RECEIVED |
| | BUT NOT ATTACHED TO THE CURRENT SET OF |
| | PLANS. |
| | |
| | 2)- HEALTH DEPARTMENT APPROVAL REQUIRED |
| | BEFORE THE ISSUANCE OF PLANS,PLAN REVIEW |
| | COMMENT FROM 01/16/2001. |
| | |
| | 3)- MECHANICAL ROOM # 26: EGRESS STAIR |
| | AS INDICATED ON PLAN (A2.1) 2'-6". |
| | SBC TABLE 1004 EITHER OCCUPANCY ASSEMBLY |
| | OR STORAGE LESS THAN 50 PEOPLE 36" STAIR |
| | WELL SEE NOTE 10. |
| | |
| | 4)- NOTE : EQUIPMENT ROOM TO BE CONSIDER |
| | ED A TRUE SECOND STORY. THE RAISED MEZZA |
| | NINE AREA MEETS 1/3RD AREA OF ROOM WITH |
| | ENCLOSED AREA BELOW.(STAIRS EXCLUDED) |
| | |
| | 5)- SHEET A2.1 CHAIRLIFT, WILL REQUIRE |
| | PRODUCT INFORMATION COMPLYING WITH |
| | FL ACCESIIBILITY CODE 4.11.2,4.2.4,4.5 |
| | 4.27 AND ASME A17.1 SAFETY CODE FOR |
| | ELEVATORS AND ESCALATORS, SEC XX,1990. |
| | |
| | 6)- SHEET A6.3 INDICATES A SECTION |
| | THROUGH THE CEILING A8.5 BUT THE DETAIL |
| | IS FOR LIGHT WELL IN FLOOR SLAB? |
| | |
| | 7)- SHEET A8.5 WOOD BLOCKING IN WALLS |
| | MISSING FIRE RETARDANT TREATED MISSING |
| | TYPE II BUILD. |
| | |
| | 8)- SHEET A9.3 INDICATE HOW COMPLIANCE |
| | WITH SBC 604. / 609.2.1 FIRE RESISTANT |
| | TREATED WOOD, SBC 803.1.2FOR DECORATIONS |
| | ? |
| | |
| | 9)- TYPE II BUILDING REQUIRES FIRE |
| | SPRINKLER DRAWINGS AS PART OF THE BUILD- |
| | ING PERMIT PACKAGE, A SEPERATE PERMIT |
| | & PLANS WILL BE REQUIRED FOR FIRE |
| | SPRINKLER PERMIT. |
| | |
| | 10)- PLANS WILL BE REQUIRED TO HAVE |
| | COUNTY IMPACT FEE STAMP BEFORE ISSUANCE. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096X8412 |