| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-07-17 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE INFORMATION/DETAIL ON | | | FIRE RATED ENCLOSURE AS CALLED OUT ON | | | DRAWING M2.2, HOOD EXHAUST ELEVATION. | | | | | | NOTE:GREASE HOOD DUCT SHALL HAVE A | | | MINIMUM OF 1" PER FOOT SLOPE | | | TOWARD HOOD AS PER 1997 SMC 505.4 | | | | | | EXHAUST OUTLET SHALL TERMINATE | | | 10' FROM ANY ADJACENT BUILDING, | | | PROPERTY LINE, WINDOW, DOOR, OR | | | AIR INTAKE | | | | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, GAS, OR WALK-IN COOLER. | | | PLEASE PROVIDE PLANS AND MANUFACTURER | | | DETAIL/ENGINEERED DRAWINGS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|