Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop M
Sequence Number 5
Notes
Date Text
2001-07-17 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE INFORMATION/DETAIL ON
 FIRE RATED ENCLOSURE AS CALLED OUT ON
 DRAWING M2.2, HOOD EXHAUST ELEVATION.
  
 NOTE:GREASE HOOD DUCT SHALL HAVE A
 MINIMUM OF 1" PER FOOT SLOPE
 TOWARD HOOD AS PER 1997 SMC 505.4
  
 EXHAUST OUTLET SHALL TERMINATE
 10' FROM ANY ADJACENT BUILDING,
 PROPERTY LINE, WINDOW, DOOR, OR
 AIR INTAKE
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, OR WALK-IN COOLER.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 DETAIL/ENGINEERED DRAWINGS.
  