Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop FIRE
Sequence Number 5
Notes
Date Text
2001-07-31 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) LEATHER BOUND WALLS SHOWN FOR
 ELEVATOR. WHAT ALLOWS THIS TO OCCUR.
 3) FIBERGLASS HOISTWAY WALLS SHOWN
 FOR ELEVATORS. CODE DOES NOT ALLOW FOR
 THIS.
 4) NO VENT SHOWN FOR HOT WATER HEATER
 VENT.
 5) MORE DETAILS NEEDED ON SMOG HOG
 GREASE FILTER UNIT SHOWN ON M2.2.
 6) EXHAUST DUCT TO SLOPE SHALL BE 1"
 PER FOOT.
 7) EXIT STAIRS LOCATED ON THE EXTERIOR
 SHALL BE SLIP RESISTANT.
 8) PLEASE SHOW HOW THE EXITS LOCATED
 ON THE MEZZANINE LEVEL MEET THE
 REQUIRED 1/2 DIAGONAL DIMENSION OF THE
 ROOM OR AREA SERVED.
  