| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-07-31 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. | | | 2) LEATHER BOUND WALLS SHOWN FOR | | | ELEVATOR. WHAT ALLOWS THIS TO OCCUR. | | | 3) FIBERGLASS HOISTWAY WALLS SHOWN | | | FOR ELEVATORS. CODE DOES NOT ALLOW FOR | | | THIS. | | | 4) NO VENT SHOWN FOR HOT WATER HEATER | | | VENT. | | | 5) MORE DETAILS NEEDED ON SMOG HOG | | | GREASE FILTER UNIT SHOWN ON M2.2. | | | 6) EXHAUST DUCT TO SLOPE SHALL BE 1" | | | PER FOOT. | | | 7) EXIT STAIRS LOCATED ON THE EXTERIOR | | | SHALL BE SLIP RESISTANT. | | | 8) PLEASE SHOW HOW THE EXITS LOCATED | | | ON THE MEZZANINE LEVEL MEET THE | | | REQUIRED 1/2 DIAGONAL DIMENSION OF THE | | | ROOM OR AREA SERVED. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|