2001-07-21 00:00:00***************** UNSAT ***************
  
  
  
 1)NOTE: PLEASE NOTE THAT PER ART;240-21-
 C-3, TRANSFORMER SEEMS TO BE MORE THAN
 10' AWAY FROM "LDP" PLEASE NOTE 10' TAP
 RULE. PLEASE PLACE NOTE ON RISER DIAGRAM
 THAT TAPS NEED TO MEET 240-21."10"TAP.
 IF OVER 10', A DISCONNECT WILL BE REQ`D.
  
 2)NOTE: PLEASE NOTE ART; 450-21-B FOR
 CLEARENCE ABOUT TRANSFORMER. PLEASE
 CALRIFY RATING OF TRANSFORMER.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372