| 2001-07-11 00:00:00 | BUILDING PLAN REVIEW |
| | TSUNAMI OF PALM BEACH |
| | 651 OKEECHOBEE BLVD# 100 |
| | PLAN REVIEW# 00110258 |
| | ARCH GGA ARCHITECT |
| | GUILLERMO GOMEZ |
| | P: (212) 628-7276 |
| | F: (212) 585-2251 |
| | |
| | ALL COMMENTS FROM THE REVIW COMPLETED |
| | ON 4/9/01 HAVE BEEN REVIEWED AND FOUND |
| | TO COMPLY WITH THE CODE. |
| | THE COMMENTS ARE MINOR IN NATURE BUT |
| | WILL REQUIRE ATTENTION TO COMPLY WITH |
| | THE CURRENT CODES. |
| | |
| | 1)- ARCH SHEET A4.1 INDICATES SOME EXTER |
| | IOR STORAGE UNDER THE EXTERIOR EXIT |
| | STAIRWAY, E 1-5&E1-6. THESE DOORS WILL |
| | REQUIRE A 3/34 HR RATING, OPENING PROTEC |
| | TIVES SEE SBC 1006.2.4. |
| | |
| | 2)- ARCH SHEET 7.1 WEST ELEVATION: |
| | KITCHEN EGRESS DOOR THE ARCH NEEDS TO BE |
| | RAISED HEADROOM CLEARENCE MAINTAINED FOR |
| | EXIT. |
| | |
| | 3)- SBC 1204.2- RESTROOMS REQUIRE |
| | FLOORS & WALLS TO BE LINED WITH NONABSOR |
| | BANT MATERIALS TO A HEIGTH OF 4'-0". |
| | |
| | 4)- FL ACCESSIBLITY CODE 1997 4.5 |
| | GROUND & FLOOR SURFACES REQUIRE SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESS- |
| | IBILE ROOMS SHALL BE FIRM, SLIP RESIST- |
| | ANT SEE ADDAAG 4.5.1 A STATIC COEFICIENT |
| | OF FRICTION OF 0.6 IS RECOMMENDED FOR |
| | ACCESSIBILE ROUTES & 0.8 FOR RAMPS. |
| | |
| | 5)- ONCE PLANS ARE APPROVED AND A CON- |
| | TRACTOR HAS SIGNED ON THE PLANS WILL |
| | NEED TO BE TAKEN TO THE COUNTY BUILDING |
| | DEPARTMENT TO BE ASSED FOR COUNTY |
| | IMPACT FEES, PLANS STAMPED AND A COPY OF |
| | IMPACT FEES PAID FOR THE CITY RECORDS. |
| | |