| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-06-27 00:00:00 | 1) NO MECHANICAL,ELECTRICAL,PLUMBING OR | | | FIRE SPRINKLER DRAWINGS PROVIDED WITH | | | PLANS. | | | 2) SITTING CHAIRS LOCATED ON THE FIRST | | | AND SECOND FLOORS STILL APPEAR TO BE | | | TOO CLOSE TOGETHER. | | | 3) PLEASE VERIFY CEILING HEIGHTS. ALL | | | CEILING HEIGHTS ARE TO BE AT LEAST 7'-6" | | | IN THE MEANS OF EGRESS. PROJECTIONS FROM | | | THE CEILINGS IN THESE AREAS CANNOT BE | | | LESS THAN 6'-8". | | | 4) SCRUBBER(S) ARE NOTED ON THE PLANS. | | | PLEASE PROVIDE MORE DETAILS. | | | 5) ALL EXTERIOR STAIRS ARE TO BE SLIP | | | RESISTANT. | | | 6) HOW WIDE IS EXTERIOR EXIT STAIR AND | | | WHAT IS ITS EXIT CAPACITY. | | | 7) HOW ARE THE PORCELAIN SOCKETS UNDER | | | THE FLOOR POWERED, PROTECTED AND ARE | | | LISTINGS PRESENT. | | | 8) MORE INFORMATION NEEDED ON KITCHEN | | | HOOD,DUCT,SCRUBBERS,AND EXTINGUISHING | | | SYSTEMS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|