2001-04-09 00:00:00BUILDING PLAN REVIEW
 TSUNAMI OF PALM BEACH
 651 OKEECHOBEE BLVD
 PLAN REVIEW: 00110258
 ARCH. GGA ARCHITECT
 GUILLERMO GOMEZ
 P (212) 628-7276
 F (212) 585-2251
  
 PARTIAL PLAN REVIEW A1.0/ A1.5, A2.0/
 A2.1M.BUILDING, FIRE & PLUMBING ARE ABLE
 TO PROVIDE A LIMITED REVIEW SINCE THE
 PLANS ARE OF FLOOR PLAN LAYOUT.
  
 1)- SBC 503.2.3. MEZANINES CAN NOT EX-
 CEED 1/3 THAT OF THE ROOM OR SPACE IN
 WHICH THEY ARE LOCATED.
  
 2)- SBC 1004.2.1 THERE SHAL BE NOT LESS
 THAN (2) APPROVED INDEPENDENT EXITS,
 ACCESSIBLE TO EACH TENANT AREA, SERVING
 EVERY STORY.
  
 3)- SBC 1004.2.2 MINIMUM NUMBER EXITS 2
 OCCUPANT LOAD PER FLOOR 1-500.
  
 4)- SBC 1005.6.2 SMOKE PROOF ENCLOSURES.
 A MINIMUM OF 2 HR FIRE RESISTANT CON-
 STRUCTION, 1 1/2 HR OPENING PROTECTIVES
 (STAIRWELL ENCLOSURES).
  
 5)- SBC 704.1 (TABLE) OCCUPANCY SEPERA-
 TION ASSEMBLY (2 HRS).
  
 6)- SBC 1011.2.3 ALL OPENINGS LOCATED
 WITHIN 10 FT. OF FIRE ESCAPES SHALL BE
 PROTECTED WITH APPROVED OPENING PROTECT-
 IVES OF AT LEAST 3/4HR FIRE RESISTANCE.
  
 THIS IS A LIMITED REVIEW OF FLOOR PLAN
 PAGES ONLY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 P (561) 659-8096 EX 8412
 F (561) 659-8026