| 2001-04-09 00:00:00 | BUILDING PLAN REVIEW | | | TSUNAMI OF PALM BEACH | | | 651 OKEECHOBEE BLVD | | | PLAN REVIEW: 00110258 | | | ARCH. GGA ARCHITECT | | | GUILLERMO GOMEZ | | | P (212) 628-7276 | | | F (212) 585-2251 | | | | | | PARTIAL PLAN REVIEW A1.0/ A1.5, A2.0/ | | | A2.1M.BUILDING, FIRE & PLUMBING ARE ABLE | | | TO PROVIDE A LIMITED REVIEW SINCE THE | | | PLANS ARE OF FLOOR PLAN LAYOUT. | | | | | | 1)- SBC 503.2.3. MEZANINES CAN NOT EX- | | | CEED 1/3 THAT OF THE ROOM OR SPACE IN | | | WHICH THEY ARE LOCATED. | | | | | | 2)- SBC 1004.2.1 THERE SHAL BE NOT LESS | | | THAN (2) APPROVED INDEPENDENT EXITS, | | | ACCESSIBLE TO EACH TENANT AREA, SERVING | | | EVERY STORY. | | | | | | 3)- SBC 1004.2.2 MINIMUM NUMBER EXITS 2 | | | OCCUPANT LOAD PER FLOOR 1-500. | | | | | | 4)- SBC 1005.6.2 SMOKE PROOF ENCLOSURES. | | | A MINIMUM OF 2 HR FIRE RESISTANT CON- | | | STRUCTION, 1 1/2 HR OPENING PROTECTIVES | | | (STAIRWELL ENCLOSURES). | | | | | | 5)- SBC 704.1 (TABLE) OCCUPANCY SEPERA- | | | TION ASSEMBLY (2 HRS). | | | | | | 6)- SBC 1011.2.3 ALL OPENINGS LOCATED | | | WITHIN 10 FT. OF FIRE ESCAPES SHALL BE | | | PROTECTED WITH APPROVED OPENING PROTECT- | | | IVES OF AT LEAST 3/4HR FIRE RESISTANCE. | | | | | | THIS IS A LIMITED REVIEW OF FLOOR PLAN | | | PAGES ONLY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | P (561) 659-8096 EX 8412 | | | F (561) 659-8026 |
|