| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-03-02 00:00:00 | DENIED; | | | | | | 1.P5 & P6 GAS SHUTOFF FOR COOKING APPL. | | | MUST BE READLY ACCESSIBLE AND | | | PROTECTED FROM DAMAGE. SGC 310.1. | | | | | | 2.SHOW SHUTOFF VALVE,AUTOMATIC SHUTOFF | | | VALVE AND UNION ONE GAS RISER DIAGRAM. | | | | | | 3.P3 NOTE 8 WASTE PIPE SHALL NOT BE | | | REDUCED BETWEEN THE CONNECTION OF THE | | | EQUIPMENT AND THE DISCHARGE POINT. | | | | | | 4.FLOOR SINKS ARE REQUIRED IN PLACE OF | | | HUB DRAINS; PLEASE MAKE THE FOLLOWING | | | CHANGES. | | | A.P3 NOTE 11 | | | B.P3 NOTE 1 | | | C.P5 GREASE WASTE RISER DIAGRAM | | | D.P6 DETAIL 10 | | | E.P7 FLOOR DRAIN SCHEDULE | | | | | | 5.P6 (9)D/M WASTE DETAIL. DISHWASHER | | | SHALL DISCHARGE TO SANITARY. DELETE | | | GREASE WASTE FROM DETAIL. | | | | | | 6.P6 (18) COOKING APPL. GAS PIPE. SHOW | | | UNION DOWN STREAM OF SOLENOID VALVE. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|