2001-02-26 00:00:00DETAIL OF ACCESS DOORS NEED TO BE
 REFLECTED ON PLANS SIZE AND LOCATION TO
 SHOW COMPLIANCE WITH 1997 SMC 304.2.
  
 MISSING PLAN A3.1M (MEZZANINE REFLECTED
 CEILING).ACCESS FOR SERVICE FOR AHU'S
 1-4 AND AHU 7 AND 8.
  
 DRAWING M1.3 - NOTE 7 IS THE FRESH AIR
 BEING BROUGHT IN BEHIND PANELS?MUST
 COMPLY WITH 97 SMC 501.2 & ASHRAE 62-89.
  
 AS PER NFPA 4-4.4.3, DUCT SMOKE
 DETECTORS WITH NOTIFICATION TO
 HORN/STROBE IN NORMALLY OCCUPIED AREA.
  
 NOTE:ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPRESSION, SUBMIT PLANS
 WITH APPLICATION.