| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-02-26 00:00:00 | DETAIL OF ACCESS DOORS NEED TO BE | | | REFLECTED ON PLANS SIZE AND LOCATION TO | | | SHOW COMPLIANCE WITH 1997 SMC 304.2. | | | | | | MISSING PLAN A3.1M (MEZZANINE REFLECTED | | | CEILING).ACCESS FOR SERVICE FOR AHU'S | | | 1-4 AND AHU 7 AND 8. | | | | | | DRAWING M1.3 - NOTE 7 IS THE FRESH AIR | | | BEING BROUGHT IN BEHIND PANELS?MUST | | | COMPLY WITH 97 SMC 501.2 & ASHRAE 62-89. | | | | | | AS PER NFPA 4-4.4.3, DUCT SMOKE | | | DETECTORS WITH NOTIFICATION TO | | | HORN/STROBE IN NORMALLY OCCUPIED AREA. | | | | | | NOTE:ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPRESSION, SUBMIT PLANS | | | WITH APPLICATION. |
|