Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-02-28 00:00:001) PLEASE PROVIDE THIS OFFICE A USAGE
 PLAN FOR THE ESTABLISHMENT. IT WAS FELT
 BY THE PLAN REVIEW STAFF THAT CERTAIN
 AREAS OF THE ESTABLISHMENT COULD BE
 CLOSED OFF FROM OTHER SECTIONS. HOW
 COULD THIS EFFECT EXITING.
 2) PLEASE INDICATE EXIT DISCHARGE
 ROUTES FROM GROUND LEVEL, NORTH SIDE
 OF BUILDING. HOW DOES EXIT DISCHARGE
 OCCUR NEAR RETAIL SERVICE DRIVE, GATES.
 3) SEATING LOCATED ALONG WEST WALL
 GROUND LEVEL IS TOO TIGHT. THESE TABLES
 AND CHAIRS DO NOT ALLOW FOR THE MINIMUM
 OF 12" BETWEEN THE BACKS OF THE CHAIRS.
 4) DOOR 12D IS NOT WIDE ENOUGH. MUST BE
 32 INCHES IN THE CLEAR.
 5) DOOR 11E AND 11F NOT WIDE ENOUGH.
 MUST BE 32 IN THE CLEAR.
 6) CRAWL SPACE TO BE FIRE SPRINKLER
 PROTECTED WHERE BAR EQUIPMENT IS STORED.
 7) DOTTED LINE NEAR 11C ON PAGE A2.1
 SIGNIFIES WHAT.
 8) FIRE SPRINKLER HEAD DISCHARGE
 PATTERNS ARE NOT TO BE AFFECTED BY THE
 FIBERGLASS PANELS.
 9) THE KITCHEN EXHAUST DUCTS THAT
 EXTEND HORIZONTALLY COULD INTERFERE WITH
 EXITING FROM THE BUILDING. PLEASE
 EXPLAIN RATIONALE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910