| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-02-28 00:00:00 | 1) PLEASE PROVIDE THIS OFFICE A USAGE | | | PLAN FOR THE ESTABLISHMENT. IT WAS FELT | | | BY THE PLAN REVIEW STAFF THAT CERTAIN | | | AREAS OF THE ESTABLISHMENT COULD BE | | | CLOSED OFF FROM OTHER SECTIONS. HOW | | | COULD THIS EFFECT EXITING. | | | 2) PLEASE INDICATE EXIT DISCHARGE | | | ROUTES FROM GROUND LEVEL, NORTH SIDE | | | OF BUILDING. HOW DOES EXIT DISCHARGE | | | OCCUR NEAR RETAIL SERVICE DRIVE, GATES. | | | 3) SEATING LOCATED ALONG WEST WALL | | | GROUND LEVEL IS TOO TIGHT. THESE TABLES | | | AND CHAIRS DO NOT ALLOW FOR THE MINIMUM | | | OF 12" BETWEEN THE BACKS OF THE CHAIRS. | | | 4) DOOR 12D IS NOT WIDE ENOUGH. MUST BE | | | 32 INCHES IN THE CLEAR. | | | 5) DOOR 11E AND 11F NOT WIDE ENOUGH. | | | MUST BE 32 IN THE CLEAR. | | | 6) CRAWL SPACE TO BE FIRE SPRINKLER | | | PROTECTED WHERE BAR EQUIPMENT IS STORED. | | | 7) DOTTED LINE NEAR 11C ON PAGE A2.1 | | | SIGNIFIES WHAT. | | | 8) FIRE SPRINKLER HEAD DISCHARGE | | | PATTERNS ARE NOT TO BE AFFECTED BY THE | | | FIBERGLASS PANELS. | | | 9) THE KITCHEN EXHAUST DUCTS THAT | | | EXTEND HORIZONTALLY COULD INTERFERE WITH | | | EXITING FROM THE BUILDING. PLEASE | | | EXPLAIN RATIONALE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|