Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop B
Sequence Number 3
Notes
Date Text
2001-02-21 00:00:00TSUNAMI RESTRAUNT
 651 OKEECHOBEE BLVD.
 PLAN REVIEW # 00110258
 GUILLERMO GOMEZ ARCH.
 PHONE (212) 628-7276
 FAX(212) 585-2251
  
 1)- SBC104.2.2 ADDITIONAL INFO:
 SHEET A1.1 THE SITE PLAN,PLEASE UPDATE
 THE SITE PLAN TO SHOW EGRESS TO AN AREA
 OF REFUGE, THE STREET OR COURTYARD.
 THERE ARE CONCERNS AS TO EXITING THIS
 AREA WITH THE AMOUNT OF PEOPLE USING THE
 EXITS AT THE REAR OF THE BUILDING AND
 BUILT IN SAFETY FACTORS, GATES ACROSS
 THE SERVICE DRIVE, HVAC EQUIPMENT AND
 EXHAUST VENTS ON THE REAR WALLS.
  
 2)- DISCREPANCIES IN PLANS, PLEASE DE-
 LETE THE FIRE EXIT RAMP ON THE SITE PLAN
 B)- A3.1 RAMP AT REAR OF LOUNGE.
 C)- A4.1 DOOR AT REAR OF LOUNGE.
  
 3)- THE LEFT SIDE OF A 2.1 IS FADED,
 NOT CLEAR AND UNREADABLE.
  
 4)- SHEETS 2.1 FIRST FLOOR AND A2.1M,
 THERE IS A CONCERN BY THE BUILDING DEPT.
 AS WELL AS THE FIRE MARSHALL TO THE
 EXITING OF THIS RESTRAUNT & LOUNGE,THERE
 IS MORE THAN ADEQUATE EXITING WHEN ALL
 ELEMENTS OF THE BUSINESS ARE OPEN. THE
 CONCERNS ARE WHEN SEGMENTS OF THE BUSI-
 NESS ARE CLOSED VIA DOORS OR GATES THAT
 THE EXITING REQUIREMENTS ARE STILL MET.
 WE CAN VISUALIZE THAT CERTAIN PORTIONS
 OF THIS RESTRAUNT HAS THREE DISTINCT
 AREASAND THE POSSIBILITY OF BEING OPEN
 AT DIFFERENT TIMES OF THE DAY. PLEASE
 PROVIDE AN OPERATION PLAN FOR THE REST-
 RAUNT & LOUNGE AREAS. WE COULD IDENTIFY
 A THIRD AREA, BAR "A" AND SURROUNDING
 RESTRAUNT AREA AS A THIRD AREA FOR
 LUNCH. ON EACH OF THESE PLANS THE ELE-
 VATOR NEEDS TO BE ACCESIBLE FOR THE
 HANDICAPPED. PLEASE IDENTIFY ALL DOORS &
 GATES THAT WOULD SEGMENT THE USAGE OF
 THESE AREAS. WE ARE LOOKING FOR ACCESS-
 IBLE ROUTES FOR EACH AREA BASED ON THE
 TIME EACH AREA MAY HAVE DIFFERENT HOURS
 OF OPERATION. INDICATE THE OCCUPANT LOAD
 ALLOWABLE FOR EACH EXIT, 50 % OF THE
 OCCUPANT LOADS MUST EGRESS THE FRONT
 ENTRY DOORS.
  
 5)- A SECOND ISSUE IS THE EGRESS TO THE
 LOUNGE (STAIRS), THIS DOESN'T ALLOW A
 ACCESSIBLE ROUTE TO THE HANDICAPPED.
  
 6)- DOORS THAT DO NOT MEET THE 32" CLEAR
 WIDTH: 11-E, 11-F & 12-D. E2.1 NOT ON
 SCHEDULE.
  
 7)- LOUNGE AREA- ADDITIONAL INFO: ON THE
 PULL OUT PLATFORM.
  
 8)- LOUNGE AREA- BAR EQUIPMENT UNDER
 PLATFORM WILL REQUIRE FIRE SPRINKLER.
  
 9)- STEEL SERVICE CATWALK: STRUCTURAL DE
 TAILS, ATTACHMENT TO THE CATWALK AS WELL
 AS THE STRUCTURE ABOVE. SBC 1003.2.3
 THE CATWALK MUST MAINTAIN A 80" VERTICAL
 CLEARENCE TO THE RAMP BELOW,MINIMUM.
 10)- SHEET A7.1 EXHAUST HOODS, EXHAUST
 GRILLS AND THE COMBUSTION AIR LOUVERS
 ARE WITHIN THE 10'-0" PROTECTED WALLS RE
 QUIRED FOR THE EMERGENCY FIRE STAIRS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412