| Plan Review Notes For Permit 00110258 |
| Permit Number |
00110258 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-17 00:00:00 | 1. PROVIDE DETAIL SHOWING ACCESSIBILITY | | | FOR AHU SERVICE SMC 304.2. NO REFERENCED | | | DWG. M3.1-M3.3, ALSO NO M5.1 DWG. | | | 2. PROVIDE ELEVATION DETAIL SHOWING | | | TERMINATION OF EXHAUST FANS AND OUTSIDE | | | AIR INTAKE OPENINGS IN RELATION TO EACH | | | OTHER & OTHER OPENINGS INTO THE | | | BUILDING INCLUDING DOORS & OPERABLE | | | WINDOWS.HAVE MINIMUM REQUIRED | | | DISTANCES SHOWN ON PLAN, PERNFPA 96 | | | 4-8.3. | | | 3. PROVIDE INFORMATION ON GREASE | | | EXHAUST DUCT LOCATION & TERMINATION | | | INCLUDING | | | SIZES SHOWING PROXIMITITY TO OTHER | | | BUILDING COMPONENTS FOR REVIEW FOR | | | COMPLIANCE WITH 1997 SMC CHAPTER 5 & | | | NFPA 96.YOUR RESPONSE (12/18/00), | | | REF. DETAIL ON DWG. M3.1., THERE WAS NO | | | SUCH DWG. SUBMITTED. | | | 4.NO VENTILATION FOR UNDERGROUND MECH. | | | RM. AS PER SMC 501.2.ALSO, THERE IS | | | NOIB-B DOOR ON SCHEDULE. | | | 5. DWG. M1.1 HAS NO NOTE #14. |
|