Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-17 00:00:001. PROVIDE DETAIL SHOWING ACCESSIBILITY
 FOR AHU SERVICE SMC 304.2. NO REFERENCED
 DWG. M3.1-M3.3, ALSO NO M5.1 DWG.
 2. PROVIDE ELEVATION DETAIL SHOWING
 TERMINATION OF EXHAUST FANS AND OUTSIDE
 AIR INTAKE OPENINGS IN RELATION TO EACH
 OTHER & OTHER OPENINGS INTO THE
 BUILDING INCLUDING DOORS & OPERABLE
 WINDOWS.HAVE MINIMUM REQUIRED
 DISTANCES SHOWN ON PLAN, PERNFPA 96
 4-8.3.
 3. PROVIDE INFORMATION ON GREASE
 EXHAUST DUCT LOCATION & TERMINATION
 INCLUDING
 SIZES SHOWING PROXIMITITY TO OTHER
 BUILDING COMPONENTS FOR REVIEW FOR
 COMPLIANCE WITH 1997 SMC CHAPTER 5 &
 NFPA 96.YOUR RESPONSE (12/18/00),
 REF. DETAIL ON DWG. M3.1., THERE WAS NO
 SUCH DWG. SUBMITTED.
 4.NO VENTILATION FOR UNDERGROUND MECH.
 RM. AS PER SMC 501.2.ALSO, THERE IS
 NOIB-B DOOR ON SCHEDULE.
 5. DWG. M1.1 HAS NO NOTE #14.