Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) PLEASE INDICATE WHERE THE 994
 ESTIMATED VISITORS TO TSUNAMI WILL
 PARK. THE FIRE LANE LOCATED ON THE
 SOUTH SIDE OF THE HIGH-RISE BUILDING
 IS TO REMAIN CLEAR AND UNOBSTRUCTED.
 PLEASE ADVISE PARKING ARRANGEMENT TO
 THIS OFFICE.
 2) PLEASE PROVIDE MORE DETAILS ON
 UNDERGROUND MECHANICAL ROOM SHOWN ON
 PAGE A2.0. NO FIRE SPRINKLERS, EMERGENCY
 LIGHTING, OR EXIT SIGNS ARE SHOWN, AND
 ONLY ONE MEANS OF EGRESS IS SHOWN.
 3) FIBERGLASS PROJECTION SCREENS ARE TO
 MEET APPLICABLE FLAME SPRED CRITERIA.
 4) DOES THE WOOD LATTICE WORK MEET
 THE APPLICABLE FLAME SPREAD CRITERIA.
 5) PLEASE EXPLAIN WHAT THE ELECTRIC
 TRANSFORMER ON PAGE A7.1 IS FOR. WHY
 IS IT LOCATED BELOW THE EXIT STAIR.
 6) WHAT PROTECTION IS PROVIDED FOR THE
 NEW FIRE RAMP SHOWN ON PAGE A7.1. IT
 APPEARS THAT THIS RAMP PASSES BY TWO
 WINDOWS AND POSSIBLY A DOOR.
 7) THE GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) PLEASE PROVIDE SET-BACK DISTANCES
 TO ADJACENT BUILDINGS, PROPERTY LINES,
 EXITS FROM THE THREE GREASE HOOD
 EXHAUST FANS.
 9) PLEASE EXPLAIN RATIONALE FOR SINGLE
 MEANS OF EGRESS FROM DINING BALCONY.
 10) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS. THESE
 ITEMS MUST BE SUBMITTED PRIOR TO
 RECEIVING A BUILDING PERMIT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497