| 2001-01-17 00:00:00 | 6). NOTE SHEET A1.2 DIVISION 17 - FIRE |
| | SUPRESSION SYSTEM, NOTE "B" TO EMBED |
| | PIPE IN CONCRETE THE GUIDELINES IN SBC |
| | 1907.3 MUST BE ADHERRED TO. WE WILL NEED |
| | THE TYPE OF PIPE, GAUGE AND SIZE OF THE |
| | PIPE TO SEE IF IT CAN QUALIFY FOR EMBED- |
| | MENT. |
| | 7). MECHANICAL ROOM STAIRS (1007.4.2) |
| | WIDTH OF LANDINGS SHALL BE NOT LESS THAN |
| | THE WIDTH OF THE STAIRWAY THEY SERVE. |
| | 8). MECHANICAL ROOM EGRESS (1004.2.1)- |
| | THERE SHALL BE NOT LESS THAN 2 APPROVED |
| | INDEPENDENT EXITS, ACCESSIBLE TO EACH |
| | TENANT AREA,SERVING EVERY "STORY-BASE- |
| | MENT." |
| | 9). SBC 104.2.2 ADDITIONAL INFORMATION- |
| | DISCREPANCY SHEET A1.4 SHOWS A REVISION |
| | #1 STAIRS TO DINING PLATFORM #4. BECAUSE |
| | OF THE OCCUPANT LOAD FOR THIS AREA 2 |
| | EGRESSES ARE REQUIRED,SHEET A1.4 SHOWS A |
| | REVISION STRIKING THE STAIRWELL AND A |
| | CONTINIOUS EGRESS PATH TO THE ELEVATOR. |
| | SHEET A.2.1M SHOWS THE SAME REVISION |
| | WITH A STAIRS TO THE PLATFORM #4 AT A |
| | HEIGTH OF 10'-6", SHEET S-2 DRAWINGS |
| | ALSO SHOW A HEIGTH OF 10'-6". THERE |
| | WOULD BE 2 CODE ITEMS TO RESOLVE. (1) |
| | THE 2 EGRESSES REQUIRED FOR THE OCCUPANT |
| | LOAD, & (2) THE ACCESSIBILITY FL ACC |
| | CODE 4.1.3 VERTICAL ACCESSIBILITY SHALL |
| | BE PROVIDED TO ALL LEVELS ABOVE & BELOW |
| | THE OCCUPIABLE GRADE LEVEL. |
| | THE SAME SITUATION WITH THE DINING BAL. |
| | THE OCCUPANT LOAD WILL REQUIRE 2 MEANS |
| | OF EGRESS. |
| | 10). FL. ACCESSIBILITY CODE 4.8.3 EGRESS |
| | RAMPS REQUIRE 44" CLEAR WIDTH. THE |
| | DOWNSTAIRS RAMP TO THE VIP PLATFORM AND |
| | THE EMERGENCY RAAMP BEHIND THE BUILDING |
| | ARE TO NARROW. |
| | 11). EMERGENCY RAMP- FL ACCESSIBILITY |
| | CODE 4.8.4.2- REQUIRES THE LANDING AT |
| | THE BOTTOM OF THE RAMP IS TO 72" LONG |
| | AND TOBE STRAIGHT & LEVEL. |
| | 12). EMERGENCY STAIRS- TO CONFORM WITH |
| | SBC 1011, SUBMIT SHOP DRAWINGS. |
| | 13). EMERGENCY FIRE STAIR (1006.2.4) |
| | SHALL SEPERATE THE INTERIOR OF THE BUILD |
| | ING BY WALLS WITH A FIRE RESISTANCE |
| | RATING OF NOT LESS THAN 1 HR., WITH FIX- |
| | ED OR SELF-CLOSING OPENING PROTECTIVES |
| | AS REQUIRED FOR CLOSED STAIRS. THIS |
| | PROTECTION SHALL EXTEND VERTICALLY FROM |
| | THE GROUND TO A POINT 10 FTABOVE THE |
| | TOPMOST LANDING. OPENINGS WITHIN 10 FT. |
| | HORIZONTAL EXTENSION OF THE PROTECTED |
| | WALLS BEYOND THE STAIRWAY SHALL BE |
| | EQUIPED WITH FIXED 3/4 HR ASSEMBLIES. |
| | THIS INCLUDES VENTS. |
| | 14). BATHROOM WALL FINISHES- SHEET A4.2 |
| | BATHROOM WALL FINISHES (SBC 1204.2) |
| | WALLS & FLOORS OF ALL PUBLIC RESTROOMS |
| | SHALL BE LINED WITH NONABSOREMENT |
| | MATERIALS TO A HEIGTH OF 4 FT ABOVE THE |
| | FLOOR. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |
| 2001-01-16 00:00:00 | 1). SBC 104.2.2SHEET A1.0 INDICATES |
| | UNDER BUILDING DATA THAT THERE IS A SEC- |
| | OND FLOOR OF 1,25 SQ FT? IS THIS SUPPOSE |
| | TO BE THE BASEMENT? |
| | 2). SBC 104.2.2 SHEET S-1 INDICATES VAR- |
| | IOUS FOOTINGS THAT WILL SIT UPON THE |
| | FOUNDATION FOR THE SHELL OF THE WHOLE |
| | BUILDING. WE WILL REQUIRE A LETTER FROM |
| | THE ENGINEER OF RECORD APPROVING THE |
| | ADDITIONAL LOADS BEING TRANSFERRED ONTO |
| | THE EXISTING FOUNDATION. |
| | 3). SHEET A1.2 DIVISION 6 NOTE #10 - |
| | ADD NOTE FOR FIRE RETARDANT TREATEDED |
| | TO PLANS. |
| | 4). MISSING FL. ENERGY SHEETS/ CALS- |
| | SIGNED ?SEALED. |
| | 5). HEALTH DEPARTMENT APPROVAL REQUIRED |
| | BEFORE THE PERMIT CAN BE ISSUED. |