Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop B
Sequence Number 2
Notes
Date Text
2001-01-17 00:00:006). NOTE SHEET A1.2 DIVISION 17 - FIRE
 SUPRESSION SYSTEM, NOTE "B" TO EMBED
 PIPE IN CONCRETE THE GUIDELINES IN SBC
 1907.3 MUST BE ADHERRED TO. WE WILL NEED
 THE TYPE OF PIPE, GAUGE AND SIZE OF THE
 PIPE TO SEE IF IT CAN QUALIFY FOR EMBED-
 MENT.
 7). MECHANICAL ROOM STAIRS (1007.4.2)
 WIDTH OF LANDINGS SHALL BE NOT LESS THAN
 THE WIDTH OF THE STAIRWAY THEY SERVE.
 8). MECHANICAL ROOM EGRESS (1004.2.1)-
 THERE SHALL BE NOT LESS THAN 2 APPROVED
 INDEPENDENT EXITS, ACCESSIBLE TO EACH
 TENANT AREA,SERVING EVERY "STORY-BASE-
 MENT."
 9). SBC 104.2.2 ADDITIONAL INFORMATION-
 DISCREPANCY SHEET A1.4 SHOWS A REVISION
 #1 STAIRS TO DINING PLATFORM #4. BECAUSE
 OF THE OCCUPANT LOAD FOR THIS AREA 2
 EGRESSES ARE REQUIRED,SHEET A1.4 SHOWS A
 REVISION STRIKING THE STAIRWELL AND A
 CONTINIOUS EGRESS PATH TO THE ELEVATOR.
 SHEET A.2.1M SHOWS THE SAME REVISION
 WITH A STAIRS TO THE PLATFORM #4 AT A
 HEIGTH OF 10'-6", SHEET S-2 DRAWINGS
 ALSO SHOW A HEIGTH OF 10'-6". THERE
 WOULD BE 2 CODE ITEMS TO RESOLVE. (1)
 THE 2 EGRESSES REQUIRED FOR THE OCCUPANT
 LOAD, & (2) THE ACCESSIBILITY FL ACC
 CODE 4.1.3 VERTICAL ACCESSIBILITY SHALL
 BE PROVIDED TO ALL LEVELS ABOVE & BELOW
 THE OCCUPIABLE GRADE LEVEL.
 THE SAME SITUATION WITH THE DINING BAL.
 THE OCCUPANT LOAD WILL REQUIRE 2 MEANS
 OF EGRESS.
 10). FL. ACCESSIBILITY CODE 4.8.3 EGRESS
 RAMPS REQUIRE 44" CLEAR WIDTH. THE
 DOWNSTAIRS RAMP TO THE VIP PLATFORM AND
 THE EMERGENCY RAAMP BEHIND THE BUILDING
 ARE TO NARROW.
 11). EMERGENCY RAMP- FL ACCESSIBILITY
 CODE 4.8.4.2- REQUIRES THE LANDING AT
 THE BOTTOM OF THE RAMP IS TO 72" LONG
 AND TOBE STRAIGHT & LEVEL.
 12). EMERGENCY STAIRS- TO CONFORM WITH
 SBC 1011, SUBMIT SHOP DRAWINGS.
 13). EMERGENCY FIRE STAIR (1006.2.4)
 SHALL SEPERATE THE INTERIOR OF THE BUILD
 ING BY WALLS WITH A FIRE RESISTANCE
 RATING OF NOT LESS THAN 1 HR., WITH FIX-
 ED OR SELF-CLOSING OPENING PROTECTIVES
 AS REQUIRED FOR CLOSED STAIRS. THIS
 PROTECTION SHALL EXTEND VERTICALLY FROM
 THE GROUND TO A POINT 10 FTABOVE THE
 TOPMOST LANDING. OPENINGS WITHIN 10 FT.
 HORIZONTAL EXTENSION OF THE PROTECTED
 WALLS BEYOND THE STAIRWAY SHALL BE
 EQUIPED WITH FIXED 3/4 HR ASSEMBLIES.
 THIS INCLUDES VENTS.
 14). BATHROOM WALL FINISHES- SHEET A4.2
 BATHROOM WALL FINISHES (SBC 1204.2)
 WALLS & FLOORS OF ALL PUBLIC RESTROOMS
 SHALL BE LINED WITH NONABSOREMENT
 MATERIALS TO A HEIGTH OF 4 FT ABOVE THE
 FLOOR.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412
2001-01-16 00:00:001). SBC 104.2.2SHEET A1.0 INDICATES
 UNDER BUILDING DATA THAT THERE IS A SEC-
 OND FLOOR OF 1,25 SQ FT? IS THIS SUPPOSE
 TO BE THE BASEMENT?
 2). SBC 104.2.2 SHEET S-1 INDICATES VAR-
 IOUS FOOTINGS THAT WILL SIT UPON THE
 FOUNDATION FOR THE SHELL OF THE WHOLE
 BUILDING. WE WILL REQUIRE A LETTER FROM
 THE ENGINEER OF RECORD APPROVING THE
 ADDITIONAL LOADS BEING TRANSFERRED ONTO
 THE EXISTING FOUNDATION.
 3). SHEET A1.2 DIVISION 6 NOTE #10 -
 ADD NOTE FOR FIRE RETARDANT TREATEDED
 TO PLANS.
 4). MISSING FL. ENERGY SHEETS/ CALS-
 SIGNED ?SEALED.
 5). HEALTH DEPARTMENT APPROVAL REQUIRED
 BEFORE THE PERMIT CAN BE ISSUED.