Plan Review Notes
Plan Review Notes For Permit 00110258
Permit Number 00110258
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001.BATHROOM FACILITYS ON FIRST FLOOR MUST
 COMPLY WITH 97 FL0RIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUTION #11
 PAGE 21 AND 4.17.
  
 2.HANDICAP LAVATORIES MUST MEET
 CLEARANCES PER FIG. #31.
  
 3.KITCHEN EQUIPMENT SCHEDULE.MINIMUM
 WASTE PIPEPIPE FROM SINKES IS 1 1/2.
 DISHWASHER AND WATER HEATER NOT LISTED
  
 4.NEED RISER DIAGRAMS FOR
 1.GREASY WASTE
 2.SANITARY WASTE
 3.WATER
 4.GAS
 5.CONDENSAT
 5.FLOOR SINKS MUST BE USED IN PLACE OF
 FLOOR DRAINS FOR INDIRECT WASTE.
  
 6.TRAP PRIMERS ARE REQUIRED FOR FLOOR
 DRAINS IN PUBLIC REST ROOMS 409.4.1.
  
 7.HOT WATER MUST BE TEMPERED TO 110F
 FOR HAND SINKS AND BATHROOM LAVATORIES
  
 8.SHOW MAKE-UP AIR AND EXHAUST FOR GAS
 WATER HEATER.
  
 9.SUBMIT GREASE TRAP DRAWINGS TO BE
 APPROVED BY RODNEY COMPO. CITY ORDIN-
 ANCE, GREASY WASTE #2938-96.
  
 10.CONDENSATE FROM AIR HANDLERS AND
 COOLERS ARE NOT PERMITED TO DUMP
 INTO CITY SEWER SYSTEM.