| 2001-01-08 00:00:00 | ************DENIED********************** |
| | |
| | 1.PROVIDE OUTSIDE AIR SCHEDULE PER |
| | ASHRAE 62-89 |
| | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING |
| | COMPLIANCE WITH 1997 SMC 501.2. |
| | 3. PROVIDE DETAIL SHOWING REQUIRED |
| | ACCESSIBILITY FOR AHU SERVICE AND MANUF- |
| | ACTURES REQUIRED COIL PULL AND OTHER |
| | MAINTAINANCE CLEARANCE REQUIREMENTS ARE |
| | DEDICATED CLEAR AREAS FOR UNIT ACCESS |
| | PER 1997 SMC 304.2 AND NEC FOR ELECTRICA |
| | CLEARANCE REQUIREMENTS |
| | 4. AHU #6 RETURN AIR PLENUM IS LOCATED |
| | IN A ROOM WITH GAS WATER HEATER. 1997 |
| | SMC 609.1.3 PROHIBITS WATER HEATERS USE- |
| | ING GAS FUEL BEING LOCATED IN THIS TYPE |
| | LOCATION. |
| | 5. PROVIDE ELEVATION DETAIL SHOWING |
| | TERMINATION OF EXHAUST FANS AND OUTSIDE |
| | AIR INTAKE OPENINGS IN RELATION TO EACH |
| | OTHER AND OTHER OPENINGS INTO THE BUILD- |
| | ING INCLUDING DOORS AND OPERABLE WINDOWS |
| | HAVE MINIMUM REQUIRED DISTANCES SHOWN ON |
| | PLAN. |
| | 6. PROVIDE INFORMATION ON GREASE EXHAUST |
| | DUCT LOCATION AND TERMINATION INCLUDING |
| | SIZES SHOWING PROXIMITY TO OTHER BUILD- |
| | ING COMPONENTS FOR REVIEW FOR COMPLIANCE |
| | WITH 1997 SMC CHAPTER 5 AND 1994 NFPA 96 |
| | 7. NOTE: SEPARATE PERMITS ARE REQUIRED |
| | FOR THE FOLLOWING SYSTEMS; HOODS, INCLUD |
| | ING GREASE DUCT AND MAKE UP AIR DUCTS AN |
| | WALKIN COOLERS AND FREEZERS. COMPLETE |
| | PLANS SHALL BE PROVIDED FOR THESE SYSTEM |
| | COMPONENTS AT TIME OF MECHANICAL PERMIT |
| | APPLICATION FOR THESE ADDITIONAL PERMITS |
| | 8. AHU 5 AND AHU 6 HAVE NO RETURN AIR |
| | PATH FROM AREA SERVED BY AHU'S |
| | 9. PRIVATE ROOM OFF BATHROOMS ON MEZZAN- |
| | INE LEVEL DOES NOT HAVE VENTILATION TO |
| | SPACE. |
| | 10.PROVIDE LOCATION OF ALL REQUIRED |
| | MANUAL VOLUME DAMPERS FOR TEST AND BALA- |
| | NACE PURPOSES. |
| | 11. SHOW LOCATIONS OF ALL FIRE DAMPERS |
| | AT RATED WALLS PER 1997 SMC 610.6 AND |
| | 610.1.2 |