Notes
Date Text
2001-01-08 00:00:001) PLEASE IDENTIFY MAIN ENTRY AND EXIT.
 THIS LOCATION IS TO PROVIDE EXITING
 FOR AT LEAST 50 PERCENT OF THE OCCUPANT
 LOAD.
 2) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 3) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 4) ALL AWNINGS ARE TO BE FIRE RETARDANT.
 5) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. ENTIRE SPACE IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL MECHANICAL, ELECTRICAL, AND SERVICE
 ROOMS. ALL VERTICAL SHAFTS ARE ALSO TO
 BE PROTECTED.
 6) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON DRAWINGS. CUT SHEETS, AND
 WIRING DIAGRAMS ARE TO BE SUBMITTED WITH
 SHOP DRAWINGS UNDER SEPARATE PERMIT.
 7) MORE DETAILS ARE NEEDED FOR THE
 PULL OUT PLATFORM. WHAT IS IT USED FOR.
 8) PLEASE DEFINE CRAWL SPACE. WHAT IS
 THIS USED FOR.
 9) ANY CHANGES IN ELEVATION LESS THAN
 21 INCHES SHALL BE BY RAMPS. STEPS WHEN
 USED ARE TO BE A MINIMUM OF THREE.
 10) THERE APPEARS TO BE TWO STEPS NEAR
 THE ELEVATOR ON THE MEZZANINE LEVEL.
 THIS WILL NOT BE PERMITTED.
 11) PLEASE EXPLAIN SLIDING WALLS.
 12) SOME GATES SWING IN AND SOME SWING
 OUT PLEASE EXPLAIN RATIONALE.
 13) PLEASE EXPLAIN SERVICE CATWALK.
 14) PLEASE BE ADVISED THAT TURNSTILES
 OR OTHER DEVICES CANNOT BE INSTALLED
 TO INTERFERE WITH THE MEANS OF EGRESS
 IN ASSEMBLY OCCUPANCIES.
 15) PLEASE CHECK INTERIOR FINISH
 NOTES. NOTES SUGGEST CLASS C, THIS
 INFORMATION APPEARS TO BE INCORRECT.
 16) PLEASE EXPLAIN CEILING HEIGHT OF
 4'-7" ON PAGE A11.4
 17) DUCT SMOKE DETECTORS REQUIRED IN
 AIR-HANDLING SYSTEMS OVER 2000CFM.
 18) ADDITIONAL EMERGENCY LIGHTING
 EQUIPMENT APPEARS TO BE NEEDED.
 19) PLEASE INDICATE PLATFORM
 CONSTRUCTION.
 20) CLEARLY EXPLAIN EXITING FROM
 MEZZANINE.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910