| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE PROVIDE MORE INFORMATION | | | ON TRANSFORMER TO CLARIFY ALL REQ`MENTS | | | OF 450-9 AND 450-21B | | | | | | 2)NOTE: PLEASE SEE E 4.2. PLEASE SEE | | | CONDUIT/CONDUCTORS AND BREAKERS FOR | | | FEEDS TO PANELS K1A AND K1B.. | | | | | | 3)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IS TO MEET LOCAL CODE OF EVERY 20` OF | | | UNENCUMBERED WALL SPACE.210-50 OF P. BCH | | | COUNTY AMENDMENTS. | | | | | | 4)NOTE: PLEASE SEE NOTE #37 ON E4.2 | | | THE CODE ART# 250-81 IS FROM THE "96" | | | NEC. PLEASE NOTE THAT WE ARE UNDER THE | | | "99" NEC AND ALL REFERENCES ON PLANS | | | NEED TO REFLECT "99" NEC. | | | | | | 5)NOTE: PLEASE PROVIDE SOME FORM OF | | | CLARIFICATION THAT LOADS FOR TRACK | | | LIGHTING IS SHOWN PER 220-12B. | | | | | | | | | 6)NOTE: PLEASE SHOW GROUNDING REQ`D BY | | | ART: 800-40 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|