| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES. BRING DRAWINGS TO THE |
| | PALM BEACH COUNTY. GET DRAWINGS |
| | STAMPED AND BRING RECEIPT. |
| | 2-SPECIFY SAFETY GLASS AT BEDRM #4 BATH |
| | AND NEW MASTER BATH HALLWAY. SEE |
| | DRAWINGS AND SECTION 2405.2 SBC 1997. |
| | 3-SPECIFY VENTILATION FOR MASTER BATH. |
| | SECTION 1203.4.2 SBC 1997. |
| | 4-PROVIDE ATTIC ACCESS AT NEW ADDITION. |
| | SECTION 2309.6 SBC 1997. |
| | 5-PROVIDE PRODUCT APPROVAL FOR: |
| | -NEW WINDOWS. |
| | -FINISH ROOFING MATERIAL. |
| | 6-CLARIFY IF THE BAHAMA SHUTTERS ARE TO |
| | BE USED FOR HURRICANE MISSILE IMPACT |
| | PROTECTION. |
| | -PROVIDE PRODUCT APPROVAL AND COMPLETE |
| | SPECIFICATIONS. |
| | 7-ENERGY CALCULATIONS: |
| | -COMPLETELY FILL THE SECOND PAGE. |
| | -OWNER/AGENT TO SIGN AND FRONT OF FORM. |
| | 8-SEE COMMENTS ON PLANS AND REVISE THE |
| | DRAWINGS AS REQUIRED. |
| | 9-ARCHITECT'S PLANS DON'T SHOW ANY INFO. |
| | CONCERNING THE EXISTING FOOTINGS. NEED |
| | INFORMATION TO VERIFY THAT EXISTING |
| | STRUCTURE WAS CONSIDERED AND IS ABLE |
| | TO SUPPORT THE ADDITIONAL LOAD. |
| | PROVIDE CALCULATIONS. |
| | |
| | NOTES: |
| | A-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | B-PLEASE RETURN REVIEWED SET OF DRAWINGS |
| | AFTER CORRECTIONS ARE DONE TO ORIGINAL |
| | DRAWINGS, IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | C-SEPARATE PERMITS WILL BE REQUIRED FOR |
| | ELECTRICAL, MECHANICAL, PLUMBING AND |
| | ROOFING WORK BECAUSE ORIGINAL PERMIT |
| | APPLICATION WAS ONLY SIGNED BY THE G.C |