| Plan Review Notes For Permit 00110201 |
| Permit Number |
00110201 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE F.A.C CHAPTER 471.025 | | | AND 61G15-23.002 . PLANS ARE TO BE SIGN- | | | -ED WITH AN ORIGINAL WET SIGNATURE. | | | | | | 2)NOTE:PLANS SHOW TRACK LIGHTING. PLEASE | | | SUBMIT LOAD CALCULATIONS FOR SERVICE | | | AND SHOW TRACK CALCS PER 220-12B | | | PLEASE SHOW SIZE OF EXISTING SERVICE. | | | | | | | | | 3)NOTE: OUTLET SPACING TO MEET LOCAL | | | CODE OF UNENCUMBERED WALL SPACE.EVERY | | | 20' OF OPEN OR REMODELED WALLS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | | | | PLEASE NOTE THAT ALL CODES REFERENCED | | | ON COVER SHEET NEED TO BE UPDATED. | | | PLEASE CALL FOR CORRECT DATES OF CODES | | | WE ARE UNDER. THE NEC IS "99" |
|