| Plan Review Notes For Permit 00110185 |
| Permit Number |
00110185 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOW THE PLANS | | | ARE SHOWING A METER/MAIN COMBO, BUT NOT | | | SHOWING AIC RATING FOR THIS. PLEASE | | | SUBMIT PER 110-9 AND 215-5. | | | | | | 2)NOTE: PLEASE SEE PLANS, THE MAIN IS | | | NOT SHOWN WITH METER. PLEASE DO SO. | | | | | | 3)NOTE: ALSO PLEASE VERIFY PANEL "A" | | | YOU SHOW ON RISER AS PANEL W/ MCB. | | | YOU HAVE MAIN ALREADY. PLEASE CHECK. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|