| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOW A MAIN DISC | | | HAS BEEN ADDED TO METER. AIC RATING OF | | | PANEL IS SHOWN BUT NOT THE AIC RATING | | | REQ`D FOR MAIN? PLEASE SUBMIT. MAIN | | | ALSO MUST BE RATED FOR THE AVAILALE | | | FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE SEE PLAN,,,THIS STILL | | | REFLECTS METER W/ NO MAIN?? CORRELATE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 ETX 8372 |
|