| 2001-02-07 00:00:00 | **************** UNSAT **************** |
| | |
| | 1)NOTE:PLEASE NOTE THAT PLANS ARE NOW |
| | SIGNED AND SEALED BY AN ENGINEER, BUT |
| | PLANS MUST CONTAIN THE TITLE BLOCK WITH |
| | ALL THE INFORMATION REQUESTED UNDER |
| | F.A.C SECTION 61G15-23.002. |
| | PLEASE CORRECT. |
| | |
| | 2)NOTE: PLEASE CLARIFY THE CONDUCTORS |
| | AND CONDUIT/RACEWAY BETWEEN METER AND |
| | FIRST DISCONNECT. SHOWS 6"X10" |
| | RACEWAY??? |
| | |
| | 3)NOTE:PLEASE NOTE THAT OLD PLANS |
| | INDICATED AIC RATING FOR NEW PANELS AND |
| | NEW PLANS DO NOT. |
| | PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRNET PER 110-9. |
| | PLEASE NOTE THAT THE NEW MAIN |
| | DISCONNECTON THE LOAD TRANSFORMER |
| | CONTAINS NO AIC RATING? |
| | |
| | 4)NOTE: PLEASE CLARIFY HOW FIRST SET OF |
| | PLANS INDICATEPANEL "HV" BEING 460` |
| | FROM METER AND NEW PLANS DO NOT MENTION |
| | THIS? PLEASE CLARIFY. MAINS MUST BE |
| | GROUPED PER 230-72 |
| | |
| | 5)NOTE: PLEASE SUBMIT PLANS SHOWING |
| | BRANCH CIRCUITS #`S THAT CORRELATE WITH |
| | PANEL SCHEDULES SUBMITTED. PLEASE NOTE T |
| | HAT THERE ARE LIGHTING CIRCUITS SHOWN AS |
| | TRANSFORMER FEEDS. |
| | PLEASE PROVIDE CLARIFICATION. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND CLARIFICATION. IF THERE |
| | ARE ANY QUESTIONS OR IF YOU WOULD LIKE T |
| | O REQUEST A MEETING TO GO OVER PLANS. |
| | PLEASE CALL. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |