| Plan Review Notes For Permit 00110159 |
| Permit Number |
00110159 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-17 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT PER SECTION | | | 553.79 6 A OF THE F.A.C. PLANS FOR | | | 277/480 ARE TO BE SIGNED AND SEALED BY | | | AN ENGINEER. | | | | | | | | | 2)NOTE: PLEASE NOTE THAT A MCB/OR MAIN | | | IS REQ`D ON THE LOAD SIDE OF | | | TRANSFORMER FOR A SEPARATELY DERIVED | | | SYSTEM. | | | | | | 3)NOTE: PLEASE PROVIDE CLARIFICATION ON | | | TRANSFORMER. RISER SHOWS NEW? PLANS FOR | | | ELECTRICAL ROOM NOTE SHOWS EXISTING | | | ELECTRICAL TRANSFORMERS? PLEASE CLARIFY. | | | | | | 4)NOTE: PLEASE PROVIDE CONDUCTOR SIZES | | | FROM METER TO MAIN.?? | | | | | | 5)NOTE: PLEASE CLARIFY THE ELEC SREVICE. | | | RISER SHOWS NEW DROP? A SECOND DROP AND | | | MEANS OF SERVICE IS ONLY PERMITTED FOR | | | SEPARATE VOLTGES NEEDED. PLEASE SHOW | | | EXISTING VOLTAGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE HAVE SIGNED AND SEALED | | | BYENGINEER. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|