Plan Review Notes
Plan Review Notes For Permit 00110159
Permit Number 00110159
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
 1.DUCTS PENETRATING RATED WALLS ARE TO
 PROTECTED PER 1997 SMC 610.1.2 AND FIRE
 DAMPERS LOCATION AND INSTALLATION DETAIL
 IS TO BE SHOWN ON THE PLAN BY THE DESIGN
 PROFESSIONAL.
 2. PROVIDE INFORMATION ON EXISTING
 EQUIPMENT SHOWING CAPACITY TO COVER NEW
 DISTRIBUTION.
 3. EXISTING DUCTWORK TO INSPECTED FOR
 CLEANLINESS AND CLEANED AND SANITIZED IF
 DEEMED NEEDED BY THE MECHANICAL INSPECTO