2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR GARAGE
 DOOR, SINGLE HUNG WINDOWS,AND OUTSWING
 DOOR.
  
 2)PROVIDE PRODUCT APPROVALS,KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS.
 INDICATE SPECIFIC TYPE OF ANCHORS TO BE
 USED.
  
 3)PROVIDE PRODUCT APPROVALS FOR ROOF
 COVERING UNDER A SEPARATE PERMIT.
  
 4)SPECIFY MEAN ROOF HEIGHT AND BEAM
 ELEVATIONS ON PLANS.
  
 5)PROVIDE NEGATIVE AND POSITIVE PRESSURE
 FOR ALL EXTERIOR WINDOW AND DOOR OPEN-
 INGS.
  
 6)PLEASE CHECK SPACING OF VERTICLE
 REINFORCEMENT IN EXTERIOR WALLS AND
 PROVIDE VERTICLE REINFORCEMENT AT EACH
 SIDE OF EXTERIOR OPENINGS.
  
 7)PROVIDE DETAILS AND SAFE LOADS FOR
 PRECAST LINTELS AT ALL EXTERIOR OPENINGS
  
 8)PROVIDE DETAIL OF WINDOW AND DOOR BUCK
 CONNECTIONS FOR WINDLOAD RESISTANCE.
  
 9)PLEASE HAVE DESIGN PROFESSIONAL
 CALCULATE UPLIFTS FOR ROOF OF STRUCTURE
 AND SPECIFY SPECIFIC CONNECTORS TO BE
 USED TO ANCHOR EACH TRUSS AND GIRDER
 TO STRUCTURE. PROVIDE THIS INFORMATION
 ON PLANS SO THAT CORRECT CONNECTORS CAN
 BE INSTALLED WHEN BOND BEAM IS POURED.
 TRUSS PLANS AND DRAWINGS ARE TO BE
 REVIEWED AND APPROVED BY DESIGNER OF
 RECORD PRIOR TO INSTALLATION OF TRUSSES.