Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE GARAGE PLAN, THERE IS
 A PANEL"A-1" SHOWN??? THIS IS NOT ON
 RISER OR MENTIONED IN NOTES?? PLEASE
 SUBMIT CLARIFICATION.215-5
 PANEL SCHEDULE FOR THIS PANEL ALSO.
  
 2)NOTE: PLEASE SEE RISER, GARAGE PANEL
 NOT SHOWN? WHERE IS THE NEW SERVICE
 GOING TO BE MOUNTED?
  
 3)NOTE: PLEASE NOTE PANEL A-1 WILL NEED
 MAIN AND SHOW GROUNDING PER NEC 250-50
  
 4)NOTE: WHERE IS PANEL "C" GOING??
  
 5)NOTE: PLEASE NOTE PER NEC 250 THE
 REQ`D COLD WATER BOND FOR GROUNDING
 ELECTRODE>
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 ARE TO HAVE LISTINGS WITH WIRE SIZES,
 BREAKER SIZES TO CORRELATE.PLEASE SUBMIT
  
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS OR
 CLARIFICATIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372
  
  
  
  
 7)NOTE: PLEASE SUBMIT COMPLETE LOAD CAL-
 -CULAATION FOR SERVICE. PER 215