| Plan Review Notes For Permit 00110151 |
| Permit Number |
00110151 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE GARAGE PLAN, THERE IS | | | A PANEL"A-1" SHOWN??? THIS IS NOT ON | | | RISER OR MENTIONED IN NOTES?? PLEASE | | | SUBMIT CLARIFICATION.215-5 | | | PANEL SCHEDULE FOR THIS PANEL ALSO. | | | | | | 2)NOTE: PLEASE SEE RISER, GARAGE PANEL | | | NOT SHOWN? WHERE IS THE NEW SERVICE | | | GOING TO BE MOUNTED? | | | | | | 3)NOTE: PLEASE NOTE PANEL A-1 WILL NEED | | | MAIN AND SHOW GROUNDING PER NEC 250-50 | | | | | | 4)NOTE: WHERE IS PANEL "C" GOING?? | | | | | | 5)NOTE: PLEASE NOTE PER NEC 250 THE | | | REQ`D COLD WATER BOND FOR GROUNDING | | | ELECTRODE> | | | | | | 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES | | | ARE TO HAVE LISTINGS WITH WIRE SIZES, | | | BREAKER SIZES TO CORRELATE.PLEASE SUBMIT | | | | | | | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS OR | | | CLARIFICATIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 | | | | | | | | | | | | | | | 7)NOTE: PLEASE SUBMIT COMPLETE LOAD CAL- | | | -CULAATION FOR SERVICE. PER 215 |
|