2001-01-08 00:00:00******************* UNSAT *************
  
 1)NOTE:PLEASE AIC RATINGS FOR ALL NEW
 EQUIPMENT BEING INSTALLED. ALL MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9..
  
 2)NOTE: PLEASE SEE RISER DIAGRAM. YOU
 SHOW 200A DISC TO 200A PANEL W/ #1 AWG??
 PLEASE SEE 310-15 AND 310-16.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER DIAGRAMS. ONE SHOWS PANEL BEING
 MLO AND THE OTHER MCB?? PLEASE CORRELATE
 THE TWO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  