| Plan Review Notes For Permit 00110106 |
| Permit Number |
00110106 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE:PLEASE AIC RATINGS FOR ALL NEW | | | EQUIPMENT BEING INSTALLED. ALL MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9.. | | | | | | 2)NOTE: PLEASE SEE RISER DIAGRAM. YOU | | | SHOW 200A DISC TO 200A PANEL W/ #1 AWG?? | | | PLEASE SEE 310-15 AND 310-16. | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULES AND | | | RISER DIAGRAMS. ONE SHOWS PANEL BEING | | | MLO AND THE OTHER MCB?? PLEASE CORRELATE | | | THE TWO. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|