| Plan Review Notes For Permit 00110100 |
| Permit Number |
00110100 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL EQUIPMENT BEING INSTALLED. MAINS/ | | | PANEL ARE TO BE RATED FOR THE AVAIL- | | | ABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES | | | AND RISER. ONE SHOWS PANELS AS MLO AND | | | THE OTHER AS MCB. | | | | | | 3)NOTE: PLEASE INCLUDE BLDG STEEL AS | | | PART OF GROUNDING ELECTRODE SYSTEM | | | PER 250-50 | | | | | | 4)NOTE: PLEASE INCLUDE THE REQ`D DEDICAT | | | -ED BATH(S) CIRCUIT(S) PER 210-11-C-3 | | | #12 AND 20A. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|