Plan Review Notes
Plan Review Notes For Permit 00110100
Permit Number 00110100
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT BEING INSTALLED. MAINS/
 PANEL ARE TO BE RATED FOR THE AVAIL-
 ABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER. ONE SHOWS PANELS AS MLO AND
 THE OTHER AS MCB.
  
 3)NOTE: PLEASE INCLUDE BLDG STEEL AS
 PART OF GROUNDING ELECTRODE SYSTEM
 PER 250-50
  
 4)NOTE: PLEASE INCLUDE THE REQ`D DEDICAT
 -ED BATH(S) CIRCUIT(S) PER 210-11-C-3
 #12 AND 20A.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372