2001-02-27 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION
 ON NOTE #1 OF FIRST REVIEWS. IS ALL
 ELECTRICAL EQUIPMENT RATED AT 22,000 AIC
 ? NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE SEE NOTE#6 FROM FIRST
 REVIEWS, ONLT ONE DISCONNECT IS SHOWN.
  
 3)NOTE: PLEASE SHOW CLARIFICATION ON
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO PANELS. SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  