| 2001-02-27 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT CLARIFICATION | | | ON NOTE #1 OF FIRST REVIEWS. IS ALL | | | ELECTRICAL EQUIPMENT RATED AT 22,000 AIC | | | ? NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE SEE NOTE#6 FROM FIRST | | | REVIEWS, ONLT ONE DISCONNECT IS SHOWN. | | | | | | 3)NOTE: PLEASE SHOW CLARIFICATION ON | | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN | | | TO PANELS. SIZE PER 250-122. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|