| Plan Review Notes For Permit 00110096 |
| Permit Number |
00110096 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | | | | ***********BUILDING UNSAT*************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | | SBCCI OR METRO DADE PRODUCT APPROVALS | | | FOR ALL EXTERIOR SWING DOORS TO BE USED | | | WITH APPROVED DRAWINGS. | | | | | | 2)PROVIDE SAFETY GLASS AS REQ PER 1997 | | | SBC 2405.2.1(3) | | | | | | 3)PROVIDE ROOF FRAMING PLAN WITH UPLIFT | | | CALCULATIONS WITH SPECIFIC CONNECTORS | | | TO BE USED. | | | | | | 4)PROVIDE TRUSS ENGINEERING SHEETS AND | | | LAYOUT PLAN. | | | | | | 5)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | | OPENINGS. |
|