| Plan Review Notes For Permit 00110096 |
| Permit Number |
00110096 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE AIC RATING SHOWN NEXT | | | TO MLO PANEL. IS THIS THE AIC RATING FOR | | | THE MAIN DISC ALSO? ALSO PLEASE NOTE | | | IF SO, THEN ALL BREAKERS IN THE 8-16 | | | PANEL ARE TO BE RATED FOR 22,00 ALSO | | | OR SHOW SERIES RATING FOR THESE. | | | | | | 2)NOTE: PLEASE SEE WIRE SIZE SHOWN FOR | | | 250A FEED FROM MAIN TO SUB-PANEL WITH | | | 1/0 AWG SHOWN. PLEASE CORRECT PER 310-16 | | | | | | 3)NOTE: PLEASE SHOW WP GFI OUTLET FOR\\ | | | A/C COND UNIT PER SEC 309.1 OF THE | | | MECH CODE. | | | | | | 4)NOTE: PLEASE SEE MISSING GFI OUTLET | | | FOR CABANA BATH PER 210-52D AND 210-11- | | | C-3. PLEASE SHOW. | | | | | | 5)NOTE: PLEASE SEE GARAGE, AHU`S SHOWN | | | IN ATTIC. PLEASE PROVIDE OUTLET PER | | | 210-63 OF THE NEC AND 309.1 | | | | | | 6)NOTE: PLEASE SHOW MAIN DISCONNECT ON | | | PLAN NEXT TO METER AS SHOWN ON RISER | | | DIAGRAM. | | | | | | 7)NOTE: PLEASE NOTE THE MISSING SMOKE | | | DETECTOR PER NFPA-72 2-2.1.1.1 IN BED- | | | -ROOM #4. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|