2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE AIC RATING SHOWN NEXT
 TO MLO PANEL. IS THIS THE AIC RATING FOR
 THE MAIN DISC ALSO? ALSO PLEASE NOTE
 IF SO, THEN ALL BREAKERS IN THE 8-16
 PANEL ARE TO BE RATED FOR 22,00 ALSO
 OR SHOW SERIES RATING FOR THESE.
  
 2)NOTE: PLEASE SEE WIRE SIZE SHOWN FOR
 250A FEED FROM MAIN TO SUB-PANEL WITH
 1/0 AWG SHOWN. PLEASE CORRECT PER 310-16
  
 3)NOTE: PLEASE SHOW WP GFI OUTLET FOR\\
 A/C COND UNIT PER SEC 309.1 OF THE
 MECH CODE.
  
 4)NOTE: PLEASE SEE MISSING GFI OUTLET
 FOR CABANA BATH PER 210-52D AND 210-11-
 C-3. PLEASE SHOW.
  
 5)NOTE: PLEASE SEE GARAGE, AHU`S SHOWN
 IN ATTIC. PLEASE PROVIDE OUTLET PER
 210-63 OF THE NEC AND 309.1
  
 6)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 PLAN NEXT TO METER AS SHOWN ON RISER
 DIAGRAM.
  
 7)NOTE: PLEASE NOTE THE MISSING SMOKE
 DETECTOR PER NFPA-72 2-2.1.1.1 IN BED-
 -ROOM #4.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372