| Plan Review Notes For Permit 00110047 |
| Permit Number |
00110047 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)DESIGN OF SANITARY SYSTEM SHALL COMPLY | | | W/SPC SECS.: | | | A)906.2.1-DRY VENTS NOT PERMITTED.BASE | | | OF STACK SHALL BE WASHED BY A FIXTURE. | | | B)FIXTURE BRANCHES NOT PERMITTED ON WET | | | VENT.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1. | | | C)FLOOR DRAIN W/TRAP PRIMER REQD.IN | | | TOILET ROOM PER SPC SEC.409.4.1.1. | | | D)SUBMIT SQUARE FEET OF HABITABLE FLOOR | | | SPACE AND OCCUPANT LOAD PER SPC TABLE | | | 407.SEE SEC.407.1.3 FOR ALLOWED DEDUCT- | | | IBLE AREAS.SUBMIT CALCULATIONS. | | | E)GRAB BARS BEHIND AND ALONGSIDE TOILET | | | SHALL COMPLY W/FACBC SEC.4.16.4. | | | F)FIXTURES SHALL BE PROPERLY VENTED.SPC | | | SEC.901.2. | | | G)SUBMIT WATER RISER DIAGRAM FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | CALL IF YOU HAVE ANY QUESTIONS. | | | 561-659-8096,EXT.8377. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|