2001-01-08 00:00:001)DESIGN OF SANITARY SYSTEM SHALL COMPLY
 W/SPC SECS.:
 A)906.2.1-DRY VENTS NOT PERMITTED.BASE
 OF STACK SHALL BE WASHED BY A FIXTURE.
 B)FIXTURE BRANCHES NOT PERMITTED ON WET
 VENT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
 C)FLOOR DRAIN W/TRAP PRIMER REQD.IN
 TOILET ROOM PER SPC SEC.409.4.1.1.
 D)SUBMIT SQUARE FEET OF HABITABLE FLOOR
 SPACE AND OCCUPANT LOAD PER SPC TABLE
 407.SEE SEC.407.1.3 FOR ALLOWED DEDUCT-
 IBLE AREAS.SUBMIT CALCULATIONS.
 E)GRAB BARS BEHIND AND ALONGSIDE TOILET
 SHALL COMPLY W/FACBC SEC.4.16.4.
 F)FIXTURES SHALL BE PROPERLY VENTED.SPC
 SEC.901.2.
 G)SUBMIT WATER RISER DIAGRAM FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL IF YOU HAVE ANY QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.