| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | 1.PAGES FROM STEPHEN K. DENNY ARE NOT | | | SEALED. | | | | | | 2.IS WATER HEATER POWER VENTED AS SHOWN | | | ON PAGE M-1 OR AS SHOWN ON A/C CONT. | | | CUT SHEET? IF POWER VENTED SUBMIT | | | MANUFACTORS SPECIFICATIONS. IF W/H | | | IS CONVENTIONAL MAKE UP AIR IS NOT | | | TO CODE. SEE SMC FIGURE 402.4A,B,C&D. | | | | | | 3.NEED SEER AND HEAT STRIP SIZE FOR | | | PACKAGE UNIT. | | | | | | 4.DRAIN SPOUT TO DRAIN TO GRASSY AREA. | | | | | | A/C PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8377 |
|