| Plan Review Notes For Permit 00110030 |
| Permit Number |
00110030 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED; | | | 1.NEED WATER HEATER MANUFACTURE'S | | | SPECIFICATIONSFOR VENTING AND MAKE UP | | | AIR. | | | 2.SUBMIT A/C EQUIPMENT SPECIFICATIONS | | | ON NEW ROOF TOP UNIT; | | | 1.MANUFACTURE | | | 2.MODEL NUMBER | | | 3.SEER VALUE | | | 4.HEAT STRIP SIZE | | | 3.NEED DIAGRAM SHOWING HOW PACKAGE | | | UNIT IS STRAPED TO ROOF TO MEET 110 | | | MPR WINDS. | | | 4.SHOW HOW CONDENSATE RUN OFF WILL BE | | | DISPOSED. |
|