| Plan Review Notes For Permit 00110030 |
| Permit Number |
00110030 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE NOTE THAT A MCB IS REQ`D | | | AT MAIN HOUSE."PANEL A" | | | | | | 2)NOTE: PLEASE NOTE THAT NEW BLDG STEEL | | | AT MAIN HOUSE TO BE BONDED ALONG WITH | | | COLD WATER PER 250-50 PLEASE SHOW. | | | | | | 3)NOTE: PLEASE SHOW SMOKE DETECTORS AS | | | REQ`D BY NFPA-72 2-2.1.1.1 INSIDE AND | | | OUTSIDE NEW BEDROOM. | | | | | | 4)NOTE: PLEASE NOTE THAT THE REQ`D DEDI- | | | -CATED BATH CIRCUIT IS NOT LISTED ON | | | PANEL SCHEDULE. PLEASE SHOW, #12,20AMP. | | | | | | 5)NOTE: MISSING OUTLET FOR KITCHEN | | | PENINSULAR PER 210-52-C-3. | | | ALL OUTLETS ERVING KITCHEN COUNTERSPACE | | | ARE TO GFI/GFI PROTECTED PER 210-8-A-6 | | | PLEASE SHOW. | | | | | | 6)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | A/C COND UNITS AT GUESTHOUSE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|