| Plan Review Notes For Permit 00110006 |
| Permit Number |
00110006 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-02-16 00:00:00 | ***************DENIED******************* | | | | | | DRAWING M-1 INDICATES RECONFIGURATION | | | OF DROPS IN KITCHEN AREA AND ADDITIONAL | | | DROPS.THIS BRINGS THE TOTAL CFM'S FOR | | | THIS AHU UP TO 1160, 2 TON UNIT IS ON | | | AIR HANDLER SCHEDULE (DWG MP-1). | | | | | | CALLED AND SPOKE WITH ALLEN, MADE HIM | | | AWARE OF THE PROBLEM.HE INDICATED THE | | | UNIT SHOULD BE A 4 TON UNIT.WILL | | | CORRECT THE PROBLEM. | | | | | | PHK 2/16/01 |
|