| Plan Review Notes For Permit 00101480 |
| Permit Number |
00101480 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *****************DENIED***************** | | | 1.1997 SMC 610.6.1 REQUIRES LOCATION AND | | | INSTALLATION DETAILS OF REQUIRED FIRE | | | DAMPERS ETC. SHALL BE SHOWN AND CLEARLY | | | IDENTIFIED ON THE PLANS BY THE DESIGNER. | | | RATED WALL AT BATTERY ROOM HAVE OPENINGS | | | IN WALLS AND NO PROTECTION SHAOWN AS | | | REQUIRED BY 610.1.2 | | | 2. CONDENSATE DRAIN LINE SHOWS TERMINATE | | | TO MOP SINK. LOCAL ORDINANCE DOES NOT | | | PERMIT CONDENSATE TO FLOW INTO SANITARY | | | SEWER. | | | 3. LOCAL CODE REQUIRES MINIMUM 18" | | | CLEARANCE BETWEEN ROOF SURFACE AND | | | BOTTOM OF EQUIPMENT SUPPORT FOR ACCESS | | | BELOW EQUIPMENT TO REROOF. |
|