Plan Review Notes
Plan Review Notes For Permit 00101433
Permit Number 00101433
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: ALL ELECTRICAL SHEETS NEED TO
 REFERENCE HC-1 FOR F.H.A REQ`MENTS.
  
 2)NOTE: PLEASE CORRELATE LOADS AND WIRE
 SIZES ON PANEL SCHEDULES TO MEET 310-16.
  
 3)NOTE: PLEASE SEE LOAD SHOWN FOR OVEN
 AT 12KW AND BRKR AT 50A? PLEASE CORRECT
  
 4)NOTE: PLEASE NOTE THAT OUTLETS SHOWN
 IN GARAGES ARE TO BE GFI/GFI PROTECTED.
 210-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096-EXT 8372