| Plan Review Notes For Permit 00101433 |
| Permit Number |
00101433 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: ALL ELECTRICAL SHEETS NEED TO | | | REFERENCE HC-1 FOR F.H.A REQ`MENTS. | | | | | | 2)NOTE: PLEASE CORRELATE LOADS AND WIRE | | | SIZES ON PANEL SCHEDULES TO MEET 310-16. | | | | | | 3)NOTE: PLEASE SEE LOAD SHOWN FOR OVEN | | | AT 12KW AND BRKR AT 50A? PLEASE CORRECT | | | | | | 4)NOTE: PLEASE NOTE THAT OUTLETS SHOWN | | | IN GARAGES ARE TO BE GFI/GFI PROTECTED. | | | 210-8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096-EXT 8372 |
|