Plan Review Notes
Plan Review Notes For Permit 00101414
Permit Number 00101414
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1- THE BOUNDRY SURVEY SHOWS A 16'-0"
 DRIVEWAY VS A PORCH ON PLANS.
 2- DISCREPANCIES IN TTHE BOUNDRY SURVEY
 & THE LOT SURVIES. LOT 55 PLANS SHOW
 A 2 STORY VS A 1 STORY ON LOT SURVEY.
 LOT 56 PLANS SHOW A 2 STORY VS A 1
 STORY ON LOT SURVEY. LOT SURVIES FOR
 57 & 58 SHOW A 2 STORY FOR BOTH!
 3-LOT #54 TABLE 600 SIDE EVEVATION 548.8
 SQ. FT. @ 10%= 54.8 S.F. WINDOW SIZE
 4.5'X5.25'=23.62/ DOOR SIZE 6'X9'=54'
 TOTAL SQ FT 77.62.(54.8 ALLOWABLE).
 4-LOT #56 MODEL C-1 SIDE ENTRY WALL AREA
 226.75'X9.33'=ALLLOWABLE OPENINGS
 249.5'X 10%=24.9'. SLID. DR 6'X8'=48SF
 REAR WALL30'X9.33'=ALLOWABLE AREA
 280.00@20%=56.00'.MASTER SUITE 32.8'+
 LIV. RM 72'=104.8'.
 5-SHEET WS-2 DETAIL #5. 2HR. DETAILNOTE:
 5/8TH INCH TYPE X DRYWALL TO BE FIRE
 CAULKED TO THE TRUSSES FOR THE 4'-0"
 EACH SIDE OF 2 HR. RATED WALL.NOTE:
 ROOF SHEATHING TO BE SEAMED AT PROPER-
 TY LINE!
 6-NOTE: FLOOD ZONE AO ZONE! FLOOD ZONE
 CERTIFICATE REQUIRED,ALL A/C &POOL
 EQUIPMENT SLABS CAN'T BE LOWER THAN
 FINISH FLOOR.
 7-SPECIFY SAFETY GLASS AT REQUIRED AREAS
 SEC. 2405.2.1.2 1997 SBC.
 8-GARAGE DOOR REPORT: THE PRODUCT APP.
 REPORTS DESIGN LOADS +31.9/ -36.8
 DOES NOT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ARCHETECT(END ZONES)
 9-PRODUCT APPROVAL (NATIONAL CERTIFIED
 TESTING LABORATORIES) TESTING REPORTS
 DO NOT SHOW THAT THEY HAVE SBCCI
 APPROVAL OR DADE COUNTY APPROVAL.
 THEY HAVE A SBCCI LAB NO 9821 SHOWING
 THAT THEY ARE AN APPROVED LAB. THE
 WINDOW MANUFACTUER WOULD NEED TOSUBMIT
 TEST RESULTS TO SBCCI FOR APPROVAL.
 THE OTHER METHOD OF APPROVAL IS WHEN
 PROFESSIONALLY DESIGNED & CERTIFIED
 TO MEET THE DESIGN LOADS & TEST
 CRITERIA, MAY BE APPROVED IN ACCORDANC
 WITH SEC. 103.7 ALTERNATE MATERIALS &
 METHODS, & AND WILL NOT REQUIRED TO
 HAVE AN EVALUATION REPORT.THE ENGINEER
 OF THE WINDOWSWOULD CERTIFY THAT
 THE WINDOWS MEET THE TESTING REQUIRE-
 MENTS FOR WIND LOADS.ENGINEER TO SIGN
 & SEAL IN CERTIFICATION BLOCK #9.
 THE ARCHETECT OF RECORD REVIEWS THAT
 THE DESIGN LOADS WILL WORK ON THIS
 SITE SPECIFIC CASE, SIGNS & SEALS IN
 BLOCK #10. ATTACHED IS A COPY OF THE
 PRODUCT APPROVAL SUBMITTAL WINDOW FORM
 10-EGRESS WINDOWS 1005.4.4 THE EGRESS
 WINDOW SIZES FROM THE WINDOW SCHEDULE
 TO THE PRODUCT APPROVAL HAVE DISCREP-
 ANCIES IN SISZES?
 11-1804.2.7.2 W.P.B. AMENDMENTS SHALL
 CONTAIN THE FOLLOWING MINIMUM INFO:
 1.A 15 FT SPT TO DETERMNE THE BASIC
 SOIL BEARING CAPACITY.
 2.SOIL PROFILES OF TTHE SUPPLEMENTAL
 10 FT AUGER REQUIRED IN T-1804.2.7.3
 3.THE MINIMUM SAFE BEARING VALUE OF THE
 SOIL.
 4.IF MUCK,SILT,TRASH,ETC THE REMOVAL &
 THE CLASSIFICATION OF NEW FILL
 MATERIAL, TEST CONTROLS.
 5.PILING, IF RECOMMENDED/SPECIFICATIONS
 6.IF ADDITIONAL FILL BE REQUIRED SPEC-
 IFICATIONS.
 12-1707.4.1 IMPACT-RESISTANT EXTERIOR
 GLAZED WINDOW/DOOR ASSEMBLIES,
 POLICY REQUIRES THERE BE A KEY PLAN
 OR DIAGRAM THAT CORRELATES WITH THE
 INSTALATION SCHEDULE.
 13-DRAFTSTOPPING 2305.2.2. FLOOR/CEILING
 ASSEMBLIES.SINGLE FAMILY DWELLINGS
 DIVIDE INTO SEPERATE USEABLE SPACES
 INTO 2 OR MORE APPROXIMATE AREAS
 WITH NO AREA GREATER THAN 500 SQ. FT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659- 8096 EX 8412.
 -PLEASE RETURN THE REVIEWED PAGES
 AFTERTHE CORRECTIONS ARE COMPLETED
 THIS WILL EXPEDITE THE REVIEW PROCESS
 THANK YOU!