| Plan Review Notes For Permit 00101333 |
| Permit Number |
00101333 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW MAINS/PANELS BEING INSTALLED. | | | THE RISER IS SHOWING AN ALL NEW SERVICE. | | | | | | 2)NOTE: PLEASE SHOW GROINDING ELECTRODE | | | SYSTEM FOR GROUND ROD AND COLD WATER | | | BOND. | | | | | | 3)NOTE: MISSING GFI OULETS FRONTAND REAR | | | OF DWELLING PER 210-52E | | | | | | 4)NOTE: MISSING OUTLET FOR GARAGE PER | | | 210-52G | | | | | | 5)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 21O-8-A-6. | | | | | | 6)NOTE: PLEASE SHOW ON PANEL SCHEDULE | | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | | PER 210-11-C-3 #12/20A | | | | | | PLANS WOULD HAVE PASSED WITH A REVISION | | | REQ`ST/PROVISO BUT WERE COMING BACK FOR | | | PLUMB AND MECH CORRECTIONS. | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|